Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 903
OFF : The output frequency is less than the value of “L4-03 - L4-04”, or it is not higher than the
value of L4-03.
Figure 11.100 Example of Frequency Detection 4 (value of L4-03 Is Positive)
■ 17: Torque Detection 1 (N.C.)
Setting Function Description
17 Torque Detection 1
(N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than the torque value set with L6-02 [Torque Detection
Level 1], or the level is less than the torque value set with L6-02 for longer than the time set with
L6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-02 for longer than the time
set in L6-03.
• Refer to “L6: Torque Detection” for more information.
■ 18: Torque Detection 2 (N.O.)
Setting Function Description
18 Torque Detection 2
(N.O.)
The terminal activates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
ON : The output current/torque is more than the torque value set with L6-05 [Torque Detection
Level 2], or the level is less than the torque value set with L6-05 for longer than the time set with
L6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-05 for longer than the time
set in L6-06.
• Refer to “L6: Torque Detection” for more information.
■ 19: Torque Detection 2 (N.C.)
Setting Function Description
19 Torque Detection 2
(N.C.)
The terminal deactivates when the drive detects overtorque or undertorque.
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than the torque value set with L6-05 [Torque Detection
Level 2], or the level is less than the torque value set with L6-05 for longer than the time set with
L6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than the detection level of L6-05 for longer than the time
set in L6-06.
• Refer to “L6: Torque Detection” for more information.