11.8 H: Terminal Functions
904 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ 1A: During Reverse
Setting Function Description
1A During Reverse
The terminal activates when the motor operates in the reverse direction.
ON : The motor is operating in the reverse direction.
OFF : The motor is operating in the forward direction or the motor stopped.
Figure 11.101 Reverse Operation Output Time Chart
■ 1B: During Baseblock (N.C.)
Setting Function Description
1B During Baseblock (N.
C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output
transistor stops switching and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
■ 1C: Motor 2 Selected
Setting Function Description
1C Motor 2 Selected
The terminal activates when motor 2 is selected.
ON : Motor 2 Selection
OFF : Motor 1 Selection
■ 1D: During Regeneration
Setting Function Description
1D During Regeneration
The terminal activates on when the motor is regenerating.
ON : Motor is regenerating.
OFF : Motor is operating or stopped.
■ 1E: Executing Auto-Restart
Setting Function Description
1E Executing Auto-
Restart
The terminal activates when the Auto Restart function is trying to restart after a fault.
The terminal deactivates when the Auto Restart function automatically resets a fault. The terminal deactivates
when the Auto Restart function detects the fault again because the Auto Restart function cannot operate when the
drive reaches the number of attempts set with L5-01 [Number of Auto Restart Attempts].
Note:
Refer to “L5: Fault Restart” for more information.