Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 907
Figure 11.102 Active Frequency Output Time Chart
■ 38: Drive Enabled
Setting Function Description
38 Drive Enabled
This terminal activates when the H1-xx = 6A [Drive Enable] terminal activates.
■ 39: Watt Hour Pulse Output
Setting Function Description
39 Watt Hour Pulse
Output
Outputs the pulse that shows the watt hours.
Note:
Refer to “H2-06: Watt Hour Output Unit Selection” for more information.
■ 3C: LOCAL Control Selected
Setting Function Description
3C LOCAL Control
Selected
The terminal activates when the Run command source or frequency reference source is LOCAL.
ON : LOCAL
The keypad is the Run command source or the frequency reference source.
OFF : REMOTE
The Run command source or frequency reference source is an external source set with b1-01 [Frequency
Reference Selection 1], b1-15 [Frequency Reference Selection 2], b1-02 [Run Command Selection 1], or b1-16
[Run Command Selection 2].
■ 3D: During Speed Search
Setting Function Description
3D During Speed Search
The terminal activates when the drive is doing speed search.
Note:
Refer to “b3: Speed Search” for more information.
■ 3E: PID Feedback Low
Setting Function Description
3E PID Feedback Low
The activates when the drive detects FbL [PID Feedback Loss].
The drive detects FbL [PID Feedback Loss] when the PID feedback value < b5-13 [PID Feedback Loss Detection
Lvl] for longer than the time set in b5-14 [PID Feedback Loss Detection Time].
Note:
Refer to “PID Feedback Loss Detection” for more information.