10 Drive Start-Up Procedure
36 YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
◆ Disable the Initial Setup Screen
Do the steps in this procedure to not show the initial start-up screen when the drive is energized.
1. Push (Home) to show the HOME screen.
Note:
• When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.
• If the screen does not show [Home] for , push (Back), and then push to show [Home].
2. Push (Menu).
3. Push / to select [Initial Setup], then push .
4. Push / to select [Show Initial Setup Screen], then push .
5. Push / to select [No], then push .
• [No]: The keypad will not show the Initial Setup Screen when the drive is energized.
• [Yes]: The keypad will show the Initial Setup Screen when the drive is energized.
◆ Control Circuit Terminal Block Functions
Hx-xx parameters set functions for the multi-function input and output terminals.
WARNING
Sudden Movement Hazard. Correctly wire and test all control circuits to make sure that the control circuits operate
correctly. If you use a drive that has incorrect control circuit wiring or operation, it can cause death or serious injury.
WARNING
Sudden Movement Hazard. Check the I/O signals and the external sequences for the drive before you set the
Application Preset function. When you set the Application Preset function (A1-06 ≠ 0), it changes the I/O terminal functions for the
drive and it can cause equipment to operate unusually. This can cause serious injury or death.
NOTICE
Damage to Equipment. Do not energize and de-energize the drive more frequently than one time each 30
minutes. If you frequently energize and de-energize the drive, it can cause drive failure.