11 Drive Control, Duty Modes, and Programming
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation 49
◆ Drive Parameters
Icon Description
The parameter is available when operating the drive with V/f Control.
The parameter is available when you operate the drive in Closed Loop V/f Control.
The parameter is available when you operate the drive in Open Loop Vector Control.
The parameter is available when you operate the drive in Closed Loop Vector Control.
The parameter is available when you operate the drive in Advanced Open Loop Vector Control.
RUN You can change the parameter setting while the drive is running.
Note:
Gray icons identify parameters that are not available in the specified control method.
This table shows the most important parameters. Refer to the table when you set parameters.
No.
(Hex.)
Name Description
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
A1-02
(0102)
Control Method Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
4 : Advanced Open Loop Vector
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
b1-01
(0180)
Frequency Reference Selection 1
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
b1-02
(0181)
Run Command Selection 1
Sets the input method for the Run command.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB