52 YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
No.
(Hex.)
Name Description
H3-12
(041A)
RUN
Terminal A2 Bias Setting
Sets the bias of the analog signal input to MFAI terminal A2.
H3-13
(041B)
Analog Input FilterTime Constant
Sets the time constant for primary delay filters on MFAI terminals.
H3-14
(041C)
Analog Input Terminal Enable Sel
Sets the enabled terminal or terminals when H1-xx = C [MFDI Function Select = Analog Terminal Enable Selection] is
ON.
1 : Terminal A1 only
2 : Terminal A2 only
3 : Terminals A1 and A2
4 : Terminal A3 only
5 : Terminals A1 and A3
6 : Terminals A2 and A3
7 : Terminals A1, A2, and A3
H4-01
(041D)
Terminal FM Analog Output Select
Sets the monitor number to send from MFAO terminal FM.
H4-02
(041E)
RUN
Terminal FM Analog Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
H4-03
(041F)
RUN
Terminal FM Analog Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
H4-04
(0420)
Terminal AM Analog Output
Select
Sets the monitoring number to be output from the MFAO terminal AM.
H4-05
(0421)
RUN
Terminal AM Analog Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
H4-06
(0422)
RUN
Terminal AM Analog Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
H4-07
(0423)
Terminal FM Signal Level Select
Sets the MFAO terminal FM output signal level.
0 : 0 to 10 Vdc
1 : -10 to +10 Vdc
2 : 4 to 20 mA
H4-08
(0424)
Terminal AM Signal Level Select
Sets the MFAO terminal AM output signal level.
0 : 0 to 10 Vdc
1 : -10 to +10 Vdc
2 : 4 to 20 mA
L1-01
(0480)
Motor Overload (oL1) Protection
Sets the motor overload protection with electronic thermal protectors.
0 : Disabled
1 : Variable Torque
2 : Constant Torque 10:1 Speed Range
3 : Constant Torque 100:1 SpeedRange
6 : Variable Torque (50Hz)
L1-02
(0481)
Motor Overload Protection Time
Sets the operation time for the electronic thermal protector of the drive to prevent damage to the motor. Usually it is not
necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV

Table of Contents

Related product manuals