12 UL Standards
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation 55
WARNING
Electrical Shock Hazard. After the drive blows a fuse or trips a GFCI, do not immediately energize the drive or
operate peripheral devices. Wait for the time specified on the warning label at a minimum and make sure that all indicators are OFF.
Then check the wiring and peripheral device ratings to find the cause of the problem. If you do not know the cause of the problem,
contact Yaskawa before you energize the drive or peripheral devices. If you do not fix the problem before you operate the drive or
peripheral devices, it can cause serious injury or death.
• 600 V class
Use the fuses specified in this document to prepare the drive for use on a circuit that supplies not more than 100,000
RMS and not more than 600 Vac when there is a short circuit in the power supply.
The user must provide branch circuit protection to protect input branch circuits as specified by the National Electric
Code (NEC), the Canadian Electric Code, Part I (CEC), and local codes.
■ 600 V Class
Table 12.2 Factory Recommended Fuses for 600 V Class
Drive Model
Semiconductor Fuse
Manufacturer: EATON/Bussmann
5382 FWH-600A
5412 FWH-600A
5472 FWH-700A
◆ Low Voltage Wiring for Control Circuit Terminals
You must provide low voltage wiring as specified by the National Electric Code (NEC), the Canadian Electric Code,
Part I (CEC), and local codes. Yaskawa recommends the NEC class 1 circuit conductor. Use the UL approved class 2
power supply for external power supply.
Table 12.3 Control Circuit Terminal Power Supplies
Input/Output Terminals Power Supply Specifications
Digital input S1 to S8, SN, SC, SP
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Analog input A1 to A3, AC, +V, -V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Analog output FM, AM, AC Uses the LVLC power supply in the drive.
Pulse train output MP, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Pulse train input RP, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Safe disable input H1, H2, HC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
Serial communication input/output D+, D-, AC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power
supply.
24 V external power supply PS, AC Use the UL Listed class 2 power supply.
◆ Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National Electric Code (NEC) and the
Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and L1-01 through L1-04 [Motor Overload Protection Select] correctly to enable motor
overload and overheat protection.
Refer to the control method and set the motor rated current with E2-01 [Motor Rated Current (FLA)].