18 Troubleshooting
76 YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Code Name Causes Possible Solutions
EF3 External Fault (Terminal S3)
MFDI terminal S3 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S3.
External Fault [H1-03 = 2C to 2F] is set to MFDI
terminal S3, but the terminal is not in use.
Correctly set the MFDI.
EF4 External Fault (Terminal S4)
MFDI terminal S4 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S4.
External Fault [H1-04 = 2C to 2F] is set to MFDI
terminal S4, but the terminal is not in use.
Correctly set the MFDI.
EF5 External Fault (Terminal S5)
MFDI terminal S5 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S5.
External Fault [H1-05 = 2C to 2F] is set to MFDI
terminal S5, but the terminal is not in use.
Correctly set the MFDI.
EF6 External Fault (Terminal S6)
MFDI terminal S6 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S6.
External Fault [H1-06 = 2C to 2F] is set to MFDI
terminal S6, but the terminal is not in use.
Correctly set the MFDI.
EF7 External Fault (Terminal S7)
MFDI terminal S7 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S7.
External Fault [H1-07 = 2C to 2F] is set to MFDI
terminal S7, but the terminal is not in use.
Correctly set the MFDI.
EF8 External Fault (Terminal S8)
MFDI terminal S8 caused an external fault through an
external device.
1. Find the device that caused the external fault and remove the
cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal S8.
External Fault [H1-08 = 2C to 2F] is set to MFDI
terminal S8, but the terminal is not in use.
Correctly set the MFDI.
EP24v External Power 24V Supply
The voltage of the main circuit power supply
decreased, and the 24 V power supply is supplying
power to the drive.
Examine the main circuit power supply.
Turn ON the main circuit power supply to run the drive.
FbH Excessive PID Feedback
The FbH detection level is set incorrectly. Adjust b5-36 [PID High Feedback Detection Lvl] and b5-37 [PID
High Feedback Detection Time].
There is a problem with the PID feedback wiring. Correct errors with the PID control wiring.
The feedback sensor is not operating correctly. Examine the sensors on the control device side.
A fault occurred in the feedback input circuit of the
drive.
Replace the control board or the drive. For information about
replacing the control board, contact Yaskawa or your nearest sales
representative.
FbL PID Feedback Loss
The FbL detection level is set incorrectly. Adjust b5-13 [PID Feedback Loss Detection Lvl] and b5-14 [PID
Feedback Loss Detection Time].
HCA High Current Alarm
The load is too heavy. Decrease the load for applications with repetitive starts and
stops.
Replace the drive with a larger capacity model.
L24v Loss of External Power 24 Supply
The voltage of the backup 24 V power supply has
decreased. The main circuit power supply is operating
correctly.
Examine the external 24 V power supply for disconnected wires
and wiring errors and repair the problems.
Examine the external 24 V power supply for problems.
LoG Com Error / Abnormal SD card
There is not a micro SD card in the keypad. Put a micro SD card in the keypad.