Parameter List
1
1.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA TOEPYAIGA8002B GA800 Drive Programming 137
No. Name Unit Default
- Drive Model - 2042 2056 2070 2082
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 6B 6D 6E 6F
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
10
(7.5)
15
(11)
15
(11)
20
(15)
20
(15)
25
(18.5)
25
(18.5)
30
(22)
L8-09
Output Ground
Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n5-02
Motor Inertia
Acceleration
Time
s 0.175 0.265 0.265 0.244 0.244 0.317 0.317 0.355
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 2110 2138 2169 2211
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 70 72 73 74
E2-11
(E4-11, E5-
02)
Motor Rated
Power
HP (kW)
30
(22)
40
(30)
40
(30)
50
(37)
50
(37)
60
(45)
60
(45)
75
(55)
b3-04
V/f Gain
during Speed
Search
% 100 80 80 80 80 80 80 80
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 2.00
b8-04
Energy Saving
Coefficient
Value
- 51.79 46.27 46.27 38.16 38.16 35.78 35.78 31.35
C5-17
(C5-37)
Motor Inertia kgm
2
0.165 0.220 0.220 0.273 0.273 0.333 0.333 0.490
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 77.2 105 105 131 131 160 160 190
E2-02
(E4-02)
Motor Rated
Slip
Hz 1.7 1.8 1.8 1.33 1.33 1.6 1.6 1.43