7-5 Registers
Monitor Registers (continued)
REGISTER
FUNCTION
BIT
DATA
DESCRIPTION
(in hex)
NO. SET
022h Communication Data Link Status 0 1 Write in Progress
1
.not used
2
not used
3
1
Upper/Lower Fault
4
1
Consistency Fault
5
not used
6
not used
7
not used
8
not used
9-15
will return zeros
023h Frequency Reference 0-15 units depend on constant n105 (1)
024h Output Frequency 0-15 units depend on constant n105 (1)
025h
Not Used
will return zeros
026h
Not Used
will return zeros
027h Output Current 0-15 (1 Amp/10) (2)
028h Output Motor Voltage 0-15 (1 Volt/1)
029h
Reserved
0-15
02Ah
Reserved
0-15
02Bh
External Terminal Input Value
0
1
Input terminal S1 is closed
1
1
Input terminal S2 is closed
2
1
Input terminal S3 is closed
3
1
Input terminal S4 is closed
4
1
Input terminal S5 is closed
5
1
Input terminal S6 is closed
6
1
not used
7
1
not used
Notes:
1. Frequency Reference unit (n103) default setting is ‘0’ (0.1Hz / 1).
2. Value in register divided by 10 equals actual amps.