EasyManua.ls Logo

YASKAWA GPD 506/P5 - Page 42

YASKAWA GPD 506/P5
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-8 Registers
Drive Parameter Registers (Read/Write)
REGISTER
PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION SETTING VALUE
101h n001 Parameter Selection /
0
n001 read & set; n002-n116 read only
Initialization
1
n001-n035 read & set;
n036-n116 read only
2
n001-n053 read & set; 1
n054-n116 read only
3
n001-n116 read & set
8
initialize for 2-wire control
9
initialize for 3-wire control
102h n002 Operation Mode Selection Run Command Frequency Ref.
0
Operator Operator
1
External Terminals Operator
2
Operator External Terminals
3
External Terminals External Terminals
4
Operator Serial Comm. 3
5
External Terminals Serial Comm.
6
Serial Comm. Serial Comm.
7
Serial Comm. Operator
8
Serial Comm. External Terminals
103h n003 Input Voltage 150.0-255.0 Volts (230V drive) 230.0
150.0-510.0 Volts (460V drive) 460.0
104h n004 Stop Method
0
Ramp to stop
1
Coast to stop 0
2
Coast to stop (Timer 1)
3
Coast to stop (Timer 2)
105h n005 Power Rotation
0
Counter clockwise 0
1
Clockwise

Related product manuals