(in hex)
FUNCTION SETTING VALUE
106h n006 Reverse Prohibit
0
Reverse Run Enabled 0
1
Reverse Run Disabled
107h n007 LOCAL/REMOTE
0
Disabled 1
key function
1
Enabled
108h n008 STOP 0 STOP key enabled when n002 set for
key function Digital Operator 1
1 STOP key enabled regardless of
programming
109h n009 Frequency Reference
Setting Method
0 ENTER key does NOT have to be
pressed to write in new data values 1
from Digital Operator 1 ENTER key does have to be pressed
to write in new data values
10Ah n010 V/f Pattern Selection 0 Fixed pattern 0
1 Custom V/f pattern
10Bh n011 Frequency – Max. 50.0 – 400.0 Hz 60.0
10Ch n012 Voltage – Max. 0.1 to 255.0 V (230V drive) 230.0
(drive output) 0.1 to 510.0 V (460V drive) 460.0 (1)
10Dh n013 Frequency - Max. Voltage Point 0.2 to 400.0 Hz 60.0 (1)
10Eh n014 Frequency - Midpoint 0.1 to 399.9 Hz 3.0 (1)
10Fh n015 Voltage - Midpoint 0.1 to 255.0 V (230V drive) 17.2
0.1 to 510.0 V (460V drive) 34.5 (1)
110h n016 Frequency - Min. (drive output) 0.1 to 10.0 Hz 1.5 (1)
111h n017 Voltage - Min. 0.1 to 50.0 V (230V drive) 11.5
0.1 to 100.0 V (460V drive) 23.0 (1)
Notes:
1. Initial value differs depending on V/f curve selected (n010 setting). Values shown are initial values when n010 is set to ‘1’.