(in hex)
FUNCTION SETTING VALUE
112h n018 Acceleration Time 1 0.0 to 3600 seconds 10.0
113h n019 Deceleration Time 1 0.0 to 3600 seconds 10.0
114h n020 Acceleration Time 2 0 to 255 seconds 10.0
115h n021 Deceleration Time 2 0 to 255 seconds 10.0
116h n022 S - curve Selection 0 No S - curve
1 0.2 sec 1
2 0.5 sec
3 1.0 sec
117h n023 Digital Operator Display Mode 0 0.1Hz
1 0.1% 0
2-39 rpm
40-4999 custom
118h n024 Frequency Reference 1 0.0 to 400.0 Hz (1) 0.0
119h n025 Frequency Reference 2 0.0 to 400.0 Hz (1) 0.0
11Ah n026 Frequency Reference 3 0.0 to 400.0 Hz (1) 0.0
11Bh n027 Frequency Reference 4 0.0 to 400.0 Hz (1) 0.0
11Ch n028 Frequency Reference 5 0.0 to 400.0 Hz (1) 0.0
11Dh n029 Frequency Reference 6 0.0 to 400.0 Hz (1) 0.0
11Eh n030 Jog Reference 0.0 to 400.0 Hz (1) 6.0
11Fh n031 Frequency Reference – Upper Limit 0 to 109% 100
120h n032 Frequency Reference – Lower Limit 0 to 100% 0
121h n033 Motor Rated Current motor FLA (within 10 to 100% of drive rated current) (2,3)
Notes:
1. Range and increment may change due to a ‘custom’ setting of n024.
2. Drive rated current is the 100% level. Setting range is 20 to 200% of the GPD506 rated current.
3. Initial value depends on GPD 506 capacity.