Setting Function Page
61
External Speed Search
command 1
–
62
External Speed Search
command 2
–
63 Field weakening –
65 KEB Ride-Thru 1 (N.C.) –
66 KEB Ride-Thru 1 (N.O.) –
67 Communications test mode –
68 High Slip Braking (HSB) –
6A Drive enable –
73 Low City Press –
75 Up 2 command –
76 Down 2 command –
7A KEB Ride-Thru 2 (N.C.) –
7B KEB Ride-Thru 2 (N.O.) –
80 HAND Mode –
81 HAND Mode 2 –
88 Volute-Thermostat Normally Open
Setting Function Page
89 Volute-Thermostat Normally Closed
8C Disable Pre-Charge –
8D Multi Setpoint 1 –
8E Multi Setpoint 2 –
8F Low Water Level –
90 High Water Level –
92 Reset Accum –
95 Remove Drive Disable –
A8 Secondary PI Disable (N.O.) –
A9 Secondary PI Disable (N.C.) –
AA Secondary PI Inverse Operation –
AB Secondary PI Integral Reset –
AC Secondary PI Integral Hold –
AD Select Secondary PI Parameters –
AF Emergency Override Forward Run –
B0 Emergency Override Reverse Run –
n
H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection
The drive has three multi-function output terminals. Table 4.21 lists the functions available for theses terminals using H2-01,
H2-02, and H2-03.
No. Parameter Name Setting Range Default
H2-01 Terminal M1-M2 Function Selection (relay) 0 to 192 37: During Frequency Output
H2-02 Terminal M3-M4 Function Selection (relay) 0 to 192 F: Through Mode
H2-03 Terminal MD-ME-MF Function Selection (relay) 0 to 192 E: Fault
Table 4.21 Multi-Function Digital Output Terminal Settings
Setting Function Page
0 During run –
1 Zero speed –
2 Speed agree 1 –
3 User-set speed agree 1 –
4 Frequency detection 1 –
5 Frequency detection 2 –
6 Drive ready –
7 DC bus undervoltage –
8 During baseblock (N.O.) –
9 Frequency reference source –
A Run command source –
B Torque detection 1 (N.O.) –
C Frequency reference loss –
D Braking resistor fault –
E Fault –
F Through mode –
10 Minor fault –
11 Fault reset command active –
12 Timer output –
13 Speed agree 2 –
14 User-set speed agree 2 –
15 Frequency detection 3 –
16 Frequency detection 4 –
Setting Function Page
17 Torque detection 1 (N.C.)
–
18 Torque detection 2 (N.O.)
19 Torque detection 2 (N.C.) –
1A During reverse –
1B During baseblock (N.C.) –
1E Restart enabled –
1F Motor overload alarm (oL1) –
20 Drive overheat pre-alarm (oH) –
22 Mechanical weakening detection –
2F Maintenance period –
30 During torque limit –
37 During frequency output –
38 Drive enabled –
39 Watt hour pulse output –
3C LOCAL/REMOTE status –
3D During speed search –
3E PID feedback low –
3F PID feedback high –
4A During KEB Ride-Thru –
4C During fast stop –
4D oH Pre-alarm time limit –
4E Braking transistor fault (rr) –
4F Braking resistor overheat (oH) –
4.6 Basic iQpump Setup and Application Preset Parameters
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
159