Single-Phase Input Sizing Method B (86% Maximum Power of Connected Motor Size)
Use single-phase input Sizing Method B for applications requiring a maximum of 86% motor power, such as a fully loaded
fan or pump that does not draw full power from motor or a fan or pump that is never run at full load.
There is no overload capacity for Sizing Method B.
Table A.18 Sizing Method B, 240 V Single-Phase Input (230 V to 240 V), 230 V Three-Phase Motor
Drive Model
Output Capacity Single Phase Input Load
Motor Power (HP) Motor FLA Power (kVA) Current (A)
2A0004 0.5 2.2 0.989 4.30
2A0006 1 4.2 1.68 7.30
2A0008 1 4.2 1.75 7.60
2A0010 1.5 6 2.44 10.6
2A0012 2 6.8 3.20 13.9
2A0018 3 9.6 4.83 21.0
2A0021 3 9.6 4.83 21.0
2A0030 4 15.2 7.82 34.0
2A0040 4 15.2 7.82 34.0
2A0056 7.5 22 11.0 48.0
2A0069 10 28 14.7 64.0
2A0081 15 42 21.2 92.0
2A0110 15 42 18.4 80.0
2A0138 20 54 23.9 104
2A0169 25 68 29.9 130
2A0211 30 80 35.4 154
2A0250 40 104 46.5 202
2A0312 50 130 57.3 249
2A0360 60 154 68.5 298
2A0415 75 192 84.2 366
Table A.19 Sizing Method B, 480 V Single-Phase Input (460 V to 480 V), 460 V Three-Phase Motor
Drive Model
Output Capacity Single Phase Input Load
Motor Power (HP) Motor FLA Power (kVA) Current (A)
4A0002 0.3 0.76 0.96 2.10
4A0004 1 2.1 1.98 4.30
4A0005 1.5 3 2.85 6.20
4A0007 2 3.4 3.59 7.80
4A0009 3 4.8 5.15 11.2
4A0011 3 4.8 5.15 11.2
4A0018 5 7.6 8.33 18.1
4A0023 5 7.6 8.33 18.1
4A0031 10 14 16.1 35.0
4A0038 10 14 16.1 35.0
4A0044 15 21 22.6 49.2
4A0058 20 27 23.9 52.0
4A0072 25 34 30.4 66.0
4A0088 25 34 30.4 66.0
4A0103 25 34 30.8 67.0
4A0139 50 65 58.0 126
4A0165 50 65 58.9 128
4A0208 60 77 70.4 153
4A0250 75 96 86.5 188
4A0296 100 124 114 248
A.4 Drive Derating Data
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
251