Drive Model
Output Capacity Single Phase Input Load
Motor Power (HP) Motor FLA Power (kVA) Current (A)
4A0362 125 156 142 308
4A0414 150 180 168 365
4A0515 150 180 171 371
4A0675 200 240 225 489
Table A.20 Sizing Method B, 600 V Single-Phase Input (575 V to 600 V), 575 V Three-Phase Motor
Drive Model
Output Capacity Single Phase Input Load
Motor Power (HP) Motor FLA Power (kVA) Current (A)
5A0003 1 1.7 1.78 3.10
5A0004 2 2.7 2.93 5.10
5A0006 3 3.9 4.37 7.60
5A0009 5 6.1 6.90 12.0
5A0011 3 3.9 4.95 8.60
5A0017 7.5 9 11.4 19.8
5A0022 7.5 9 11.4 19.8
5A0027 10 11 16.1 28.0
5A0032 10 11 16.1 28.0
5A0041 20 22 24.0 41.8
5A0052 20 22 24.0 41.8
5A0062 30 32 36.8 64.0
5A0077 40 41 46.0 80.0
5A0099 40 41 47.2 82.0
5A0125 60 62 68.4 119
5A0145 60 62 68.4 119
5A0192 100 99 113 196
5A0242 100 99 113 196
u
Temperature Derating
To ensure the maximum performance life, the drive output current must be derated as shown in Figure A.1 when the drive is
installed in areas with high ambient temperature or if drives are mounted side-by-side in a cabinet. In order to ensure reliable
drive overload protection, set parameters L8-12 and L8-35 according to the installation conditions.
n
Parameter Settings
No. Name Description Range Def.
L8-12
Ambient
Temperature Setting
Adjust the drive overload (oL2) protection level when the drive is installed
in an environment that exceeds its ambient temperature rating.
-10 to +50 +40 °C
L8-35
Installation Method
Selection
0: IP00/Open-Chassis Enclosure
1: Side-by-Side Mounting
2: IP20/NEMA Type 1 Enclosure
3: Finless Drive or External Heatsink Installation
0 to 3
<1>
<1> Default setting is determined by drive model.
Setting 0: (Models 2A0250 to 2A0415 and 4A0208 to 4A0675)
Setting 2: (Models 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242).
IP00/Open-Chassis Enclosure
Drive operation between -10 °C and +50 °C allows 100% continuous current without derating.
Side-by-Side Mounting
Drive operation between -10 °C and +30 °C allows 100% continuous current without derating. Operation between +30 °C and
+50 °C requires output current derating.
IP20/NEMA Type 1 Enclosure
Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and
+50 °C requires output current derating.
A.4 Drive Derating Data
252
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide