H2 Multi-Function Digital Output Settings
H2-oo
Setting
Function LCD Display Description Page
84 Pump 6 Control Pump 6 Control
Contactor control for a sixth pump.
The function is active in contactor multiplex mode only (P1-01 = 1) and when
P3-01 is set to a value greater than 4.
89 Output 1 Limit Output I Lim
Closed: Drive output speed is being limited due to the output current limit or the
single phase foldback regulator.
8B Lube Pump Lube Pump Closed: Energizes for the time set in P4-31 each time the drive is supposed to start.
8F Internal Fan On Internal Fan On Internal Fan On
91 Pump Fault Pump Fault
Closed when any of the following faults are active:
Low feedback
High feedback
Low water
High water
NMS-Setpoint not met
POC-Pump over cycle
THMS-Thermostat input
External pump fault
92 Transducer Loss Transducer Loss
Closed: The analog output associated with PID feedback has risen above 21 mA
or fallen below 3 mA or a Transducer Loss alarm or fault is active.
93 Setptoint Not Met SetPoint Not Met Closed: During an “NMS-Setpoint Not Met” condition.
94 Loss of Prime Loss of Prime Closed: During an “LOP-Loss of Prime” condition.
95 Volute Thermostat Fault Volute-TStat Flt Closed: Volute-Thermostat digital input is active.
96 High Feedback High Feedback
Closed: During a “High Feedback” condition as defined by P1-11 and P1-12 OR
Closed: During a “High FB/Water” fault OR
Closed: During a “High Feedback” alarm
97 Low Feedback Low Feedback
Closed: During a “Low Feedback” condition as defined by P1-08 and P1-12 OR
Closed: During a “Low FB/Water” fault OR
Closed: During a “Low Feedback” alarm
98 Low Flow Low Flow
Closed: During the “Low Flow Fault” condition OR
Closed: During a Low Flow condition set by P6-06 to P6-08, including a “Low
Flow” alarm
99 Accum Level Accum Level
Closed: Accumulated level has exceeded the P6-11 to P6-14 settings OR
Closed: During the “Accum Level” fault
9A High Flow High Flow
Closed: During the “High Flow Fault” condition OR
Closed: During a “High Flow” condition set by P6-17 and P6-18, including a “High
Flow” alarm
9B Low Water Level Low Water Level
Closed: The water level has dropped below the Low Detection Level set in Q4-09
for longer than the Low Level Detection Delay Time set in Q4-09 or if there is a
LOWWL – Low Water Level Fault.
9C Low Suction Low Suction
Closed: The suction pressure has dropped below the Low Suction Pressure
Detection Level set in Q5-09 for longer than the Low Suction Pressure Delay Time
set in Q5-10 or if there is a LOSUC – Low Suction Pressure Fault.
9D High Suction High Suction
Closed: The suction pressure has risen above the High Suction Pressure Detection
Level set in Q5-12 for longer than the High Suction Pressure Delay Time set in
Q5-13 or if there is a HISUC – High Suction Pressure Fault.
A2 Sleep Active Sleep Active
Closed: The drive is not running due to the Sleep function (does not include Sleep
Boost).
A3 Start Delay Start Delay
Closed: Feedback has risen above the start level (or fallen below for Inverse PID)
and the start timer is timing.
A4 Pre-Charge Pre-Chg Active Closed: Drive is in Pre-Charge mode.
A5 Anti-Jam Active Anti-Jam Active
Closed: The anti-jam function is active (configured by P7-oo).
A9 Thrust Mode Thrust Mode
Closed: The Thrust Bearing feature is active (output frequency is between 0 and
the value of P4-12).
AA Utility Start Delay Utility Delay
Closed: The drive is stopped and waiting for the utility delay timer set in P4-17 to
expire.
100 to
1AA
Function 0 to AA with
inverse output
Inverts the output switching of the multi-function output functions.
Set the last two digits of 1oo to reverse the output signal of that specific function.
B.7 H Parameters: Multi-Function Terminals
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
283