No.
(Addr.
Hex)
Name LCD Display Description Values Page
H3-17
(02F1)
Terminal A2 Offset Term A2 Offset Adds an offset when the analog signal to terminal A2 is at 0 V.
Default: 0
Min.: -500
Max.: 500
–
H3-18
(02F2)
Terminal A3 Offset Term A3 Offset Adds an offset when the analog signal to terminal A3 is at 0 V.
Default: 0
Min.: -500
Max.: 500
–
H3 Multi-Function Analog Input Settings
H3-oo
Setting
Function LCD Display Description Page
0 Frequency bias Freq Ref Bias 10 V = E1-04 (maximum output frequency) –
1 Frequency gain Freq Ref Gain
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting
of -100 to 0%.
–
2
Auxiliary frequency
reference 1
Aux Reference1
10 V = E1-04 (maximum output frequency)
–
3
Auxiliary frequency
reference 2
Aux Reference2
10 V = E1-04 (maximum output frequency)
–
4 Output voltage bias Voltage Bias
V/fV/f
10 V = E1-05 (motor rated voltage)
–
5 Accel/decel time gain Acc/Dec Change 10 V = 100% –
6
DC Injection Braking
current
DC Brake Current
10 V = Drive rated current
–
7
Overtorque/
undertorque
detection level
Torque Det Level
10 V = Drive rated current (V/f)
–
8
Stall Prevention level
during run
Stall Prev Level
V/fV/f
10 V = Drive rated current
–
9
Output frequency lower
limit level
Ref Lower Limit
10 V = E1-04 (maximum output frequency)
–
B PID feedback PID Feedback1 10 V = 100% –
C PID setpoint PID Set Point 10 V = 100% –
D Frequency bias Freq Ref Bias 2 10 V = E1-04 (maximum output frequency) –
E
Motor Temperature
(PTC Input)
E Motor PTC
10 V = 100%
Note:
A 12 kΩ resistor must be connected between terminals A1, A2, or
A3 and V+ for PTC functionality.
–
F Through mode Not Used
Select this setting when using the terminal in a pass-through mode. The terminal
does not trigger a drive function but can be used as digital input for the controller
the drive is connected to.
–
10 Forward torque limit Fwd Torque Limit
OLVOLVOLVOLV
10 V = Motor rated torque
–
11 Reverse torque limit Rev Torque Limit
OLVOLVOLVOLV
10 V = Motor rated torque
–
12
Regenerative torque
limit
Regen Torq Limit
OLVOLVOLVOLV
10 V = Motor rated torque
–
15 General torque limit Torque Limit
OLVOLVOLVOLV
10 V = Motor rated torque
–
16
Differential PID
feedback
PID Feedback 2
10 V = 100%
–
1F Through mode Not Used Set this value when using the terminal in the pass-through mode. –
20
HAND Frequency
Reference
Hand Freq. Ref. Full scale: Max. frequency (E1-04) –
21
Geothermal
Temperature
Geothermal Temp
Full scale: Q2-02 = 10 V (or 20 mA), Q2-01 = 0 V (or 4 mA)
This input is internally limited to -110.0 °F to +320.0 °F after gain and bias.
–
22 Flow Meter Flow Meter Full scale: P6-01 –
B.7 H Parameters: Multi-Function Terminals
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
285
B
Parameter List