u
H6: Pulse Train Input
No.
(Addr.
Hex)
Name LCD Display Description Values Page
H6-01
(042C)
Pulse Train Input
Terminal RP Function
Selection
Term RP Func Sel
0: Frequency Ref
1: PID Feedback
2: PID Set Point
5: Flow Meter
0: Frequency reference
1: PID feedback value
2: PID setpoint value
5: Flow meter
Note: When this parameter is set to 5, parameters H6-02
to H6-04 and H6-08 are ignored.
Default: 0
Range: 0 to 2; 5
H6-02
(042D)
Pulse Train Input
Scaling
Term RP Scaling
Sets the terminal RP input signal frequency that is equal to 100%
of the value selected in H6-01.
Default: 1440 Hz
Min.: 100
Max.: 32000
H6-03
(042E)
Pulse Train Input Gain Term RP Gain
Sets the level of the value selected in H6-01 when a frequency
with the value set in H6-02 is input.
Default: 100.0%
Min.: 0.0
Max.: 1000.0
H6-04
(042F)
Pulse Train Input Bias Term RP Bias
Sets the level of the value selected in H6-01 when 0 Hz is input.
Default: 0.0%
Min.: -100.0
Max.: 100.0
H6-05
(0430)
Pulse Train Input Filter
Time
Term RP Flt Time
Sets the pulse train input filter time constant.
Default: 0.50 s
Min.: 0.00
Max.: 2.00
H6-08
(043F)
Pulse Train Input
Minimum Frequency
RP Lower Limit
Sets the minimum frequency for the pulse train input to be
detected. Enabled when H6-01 = 0, 1, or 2.
Default: 0.5 Hz
Min.: 0.1
Max.: 1000.0
B.7 H Parameters: Multi-Function Terminals
288