Name LCD Display Description Values Page
L2-04
(0488)
Momentary Power Loss
Voltage Recovery
Ramp Time
PwrL V/F Ramp t
Sets the time for the output voltage to return to the preset V/f
pattern during Speed Search.
Default:
<1>
Min.: 0.0 s
Max.: 5.0 s
L2-05
(0489)
Undervoltage Detection
Level (Uv1)
PUV Det Level
Sets the DC bus undervoltage trip level. Default: 190
Vdc
<2> <3>
Min.: 150 Vdc
Max.: 210 Vdc
<3>
L2-06
(048A)
KEB Deceleration
Time
KEB Decel Time
Sets the time required to decelerate from the speed when KEB
was activated to zero speed.
Default: 0.00 s
Min.: 0.00
Max.: 6000.0
<4>
L2-07
(048B)
KEB Acceleration
Time
KEB Accel Time
Sets the time to accelerate to the frequency reference when
momentary power loss is over. If set to 0.0, the active
acceleration time is used.
Default: 0.00 s
Min.: 0.00
Max.: 6000.0
<4>
L2-08
(048C)
Frequency Gain at KEB
Start
KEB Freq Red
Sets the percentage of output frequency reduction at the
beginning of deceleration when the KEB Ride-Thru function is
started.
Reduction = (slip frequency before KEB) × L2-08 × 2
Default: 100%
Min.: 0
Max.: 300
L2-10
(048E)
KEB Detection Time
(Minimum KEB Time)
KEB Detect Time
Sets the time to perform KEB Ride-Thru. Default: 50 ms
Min.: 0
Max.: 2000
L2-11
(0461)
DC Bus Voltage
Setpoint during KEB
KEB DC Bus Level
Sets the desired value of the DC bus voltage during KEB Ride-
Thru.
Default:
<2>
[E1-01] × 1.22
Min.: 150 Vdc
Max.: 400 Vdc
<5>
L2-29
(0475)
KEB Method Selection
KEB Mode Sel
0: Single Mode KEB1
1: Single Mode KEB2
2: System Mode
KEB1
3: System Mode
KEB2
0: Single Drive KEB Ride-Thru 1
1: Single Drive KEB Ride-Thru 2
2: System KEB Ride-Thru 1
3: System KEB Ride-Thru 2
Default: 0
Range: 0 to 3
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting is dependent on parameter E1-01, Input voltage Setting.
<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting range
becomes 0.00 to 600.00 seconds.
<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives, but
set the value below 1040 Vdc (overvoltage protection level).
u
L3: Stall Prevention
No.
(Addr.
Hex)
Name LCD Display Description Values Page
L3-01
(048F)
Stall Prevention
Selection during
Acceleration
StallP Accel Sel
0: Disabled
1: General purpose
2: Intelligent
0: Disabled.
1: General purpose. Acceleration is paused as long as the current
is above the L3-02 setting.
2: Intelligent. Accelerate in the shortest possible time without
exceeding the L3-02 level.
Default: 1
Range: 0 to 2
L3-02
(0490)
Stall Prevention Level
during Acceleration
StallP Accel Lvl
Used when L3-01 = 1 or 2. 100% is equal to the drive rated
current.
Default:
<1>
Min.: 0%
Max.: 150%
<1>
L3-03
(0491)
Stall Prevention Limit
during Acceleration
StallPAcc LowLim
Sets Stall Prevention lower limit during acceleration when
operating in the constant power range. Set as a percentage of
drive rated current.
Default: 50%
Min.: 0
Max.: 100
B.8 L: Protection Function
290
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide