YASKAWA iQpump1000 - HOA KEYPAD DISPLAY MESSAGES

YASKAWA iQpump1000
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name LCD Display Description Values Page
L8-10
(04B6)
Heatsink Cooling Fan
Operation Selection
Fan On/Off Sel
0: Dur Run (OffDly)
1: Always On
0: During run only. Fan operates only during run for L8-11
seconds after stop.
1: Fan always on. Cooling fan operates whenever the drive is
powered up.
Default: 0
Range: 0, 1
L8-11
(04B7)
Heatsink Cooling Fan
Off Delay Time
Fan Delay Time
Sets a delay time to shut off the cooling fan after the Run
command is removed when L8-10 = 0.
Default: 300 s
Min.: 0
Max.: 300
L8-12
(04B8)
Ambient Temperature
Setting
Ambient Temp
Enter the ambient temperature. This value adjusts the oL2
detection level.
Default: 40 °C
Min.: -10
Max.: 50
L8-15
(04BB)
oL2 Characteristics
Selection at Low
Speeds
OL2 Sel @ L-Spd
0: Disabled
1: Enabled
0: No oL2 level reduction below 6 Hz.
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0 Hz.
Default: 1
Range: 0, 1
L8-18
(04BE)
Software Current Limit
Selection
Soft CLA Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
L8-19
(04BF)
Frequency Reduction
Rate during Overheat
Pre-Alarm
Fc Red dur OHAlm
Specifies the frequency reference reduction gain at overheat pre-
alarm when L8-03 = 4.
Default: 0.8
Min.: 0.1
Max.: 0.9
L8-32
(04E2)
Main Contactor and
Cooling Fan Power
Supply Failure
Selection
MC/FAN PS FltSel
0: Ramp to stop
1: Coast to stop
2: Fast-Stop
3: Alarm only
4: Run@L8-19 Rate
Determines drive response when a fault occurs with the internal
cooling fan.
0: Ramp to stop
1: Coast to stop
2: Fast stop (Decelerate to stop using the deceleration time set
to C1-09)
3: Alarm only (“FAn” will flash)
4: Continue operation at reduced speed as set to L8-19.
Default: 1
Range: 0 to 4
L8-35
(04EC)
Installation Method
Selection
Installation Sel
0: IP00/OpenChassis
1: Side-by-Side
2: IP20/Nema Type 1
3: ExternalHeatsink
0: IP00/Open-Chassis enclosure
1: Side-by-Side mounting
2: IP20/NEMA Type 1 enclosure
3: Finless model drive or external heatsink installation
Default:
<2> <3>
Range: 0 to 3
L8-38
(04EF)
Carrier Frequency
Reduction
Fc Reduct dur OL
0: Disabled
1: Active below 6Hz
2: Active @ any Spd
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the entire speed range
Default: 2
Range: 0 to 2
L8-40
(04F1)
Carrier Frequency
Reduction Off Delay
Time
Fc Reduct Time
Sets the time that the drive continues running with reduced
carrier frequency after the carrier reduction condition is gone.
Setting 0.00 s disables the carrier frequency reduction time.
Default: 0.5 s
Min.: 0.00
Max.: 2.00
L8-41
(04F2)
High Current Alarm
Selection
High Cur Alm Sel
0: Disabled
1: Enabled
0: Disabled
1: Enabled. An alarm is triggered at output currents above 150%
of drive rated current.
Default: 0
Range: 0, 1
L8-55
(045F)
Internal Braking
Transistor Protection
FC Sel dur OHAlm
0: Disabled
1: Enabled
0: Disabled. Disable when using a regen converter or optional
braking unit.
1: Protection enabled.
Default: 1
Range: 0, 1
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is determined by the drive model:
Setting 2: Model code 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242
Setting 0: Model code 2A0250 to 2A0415 and 4A0208 to 4A0675
B.8 L: Protection Function
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
295
B
Parameter List

Table of Contents