Name LCD Display Description Values Page
P3-11
(0CD2)
Setpoint Boost after De-
Stage Time
SP Boost Time
Sets the amount of time that the setpoint will remain boosted
after lag pump is de-staged.
Default: 5.0 s
Min.: 0.0
Max.: 60.0
P3-12
(0CD3)
Multi Pump Setpoint
Increase during
Transition
MP Setpoint Inc
Sets the system setpoint increase each time a new pump is
brought online.
Pump 1: Setpoint
Pump 1 + 2: Setpoint + P3-12
Pump 1 + 2 + 3: Setpoint + 2 x P3-12
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
P3-13
(0CD4)
Multi Pump Setpoint
Decrease during
Transition
MP Setpoint Dec
Sets the system setpoint decrease each time a new pump is
brought online.
Pump 1: Setpoint
Pump 1 + 2: Setpoint - P3-13
Pump 1 + 2 + 3: Setpoint - 2 x P3-13
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 6000.0
P3-14
(0CD5)
Multiplex Stabilization
Time
M-Stabilize Time
Sets the time used to stabilize the system when a pump is added
or shut down during multiplex operation.
When a pump is added, the stabilize timer temporarily disables
the lead/lag functionality for the programmed time to prevent
pump cycling.
Function is active in contactor multiplex mode (P1-01 = 1).
Time pump protection and lead/lag control is suspended during
stabilization time.
Default: 2 s
Min.: 0
Max.: 3600
P3-30
(0CD5)
Stage Selection Mode
Stage Sel Mode
0: Sequential
1: Stop History
Sets the method of staging for the pumps.
0: Sequential
1: Stop history
Default: 0
Range: 0, 1
P3-31
(0CE6)
De-Stage Selection
Mode
Destage Sel Mode
0: LastInFirstOut
1: FirstInFirstOut
Sets the method for removing contactor pumps.
0: Last in, first out (LIFO)
1: First in, first out (FIFO)
Default: 0
Range: 0, 1
P3-40
(0CEF)
Pre-Charge Lag Pump
Select
Precharge LagSel
0: Disabled
2: Pump2 (H2-0X=80)
3: Pump3 (H2-0X=81)
4: Pump4 (H2-0X=82)
5: Pump5 (H2-0X=83)
6: Pump6 (H2-0X=84)
Selects which of the lag pumps can come on during a pre-charge.
0: Disabled
2: Pump 2 (H2-0o = 80)
3: Pump 3 (H2-0o = 81)
4: Pump 4 (H2-0o = 82)
5: Pump 5 (H2-0o = 83)
6: Pump 6 (H2-0o = 84)
Default: 0
Range: 0; 2 to 6
P3-41
(0CF0)
Pre-Charge Lag Pump
Run Time
Precharge Lag Tm
Sets the length of time that the lag pump specified in P3-40 is
energized.
Default: 0.0 min
Min.: 0.0
Max.: 3600.0
P3-42
(0CF1)
Post-Pre-Charge Lag
Pump Operation Time
Post PreChg Lag
0: Turn Off
1: Continue
Determines whether the lag pump set in pre-charge (P3-40)
turns off or maintains its state when pre-charge is completed.
0: Turn off
1: Continue
Default: 0
Range: 0, 1
P3-43
(0CF2)
Pre-Charge Lag Pump
Delay Time
PreChg Lag Delay
Sets the length of time that the drive is in the pre-charge mode
before the lag pump set in P3-40 is energized.
Default: 2.0 min
Min.: 0.0
Max.: 600.0
P3-50
(0CF9)
Pump 2 Frequency
Shutdown Level
P2 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
When P3-02 is set to 0 and a total of two pumps are running, the
last pump (Pump 2) that was brought online will be shut down
by opening the dedicated mult-function discrete output
(H2-0o = 80 to 84) when the output frequency falls below the
level set in this parameter for the time set in P3-09.
When P3-02 is set to 2 and a total of two pumps are running, the
last pump (Pump 2) that was brought online will be shut down
by opening the dedicated mult-function discrete output
(H2-0o = 80 to 84) when the delta feedback (setpoint minus
feedback) has exceeded the level programmed in this parameter
for the time set in P3-09.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
167
P3-60
(11E5)
Pump 3 Frequency
Shutdown Level
P3 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 3
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0
167
P3-70
(11EF)
Pump 4 Frequency
Shutdown Level
P4 Shutdown Freq
Sets the level used for the multiplex pumping operation.
Parameter is active only when P3-02 is set to 0 or 2.
Parameter function is similar to P3-50, except for Pump 4
instead of Pump 2.
Default: 40.0 Hz
Min.: 0.0
Max.: 400.0