YASKAWA iQpump1000 - Peripheral Devices & Options

YASKAWA iQpump1000
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name LCD Display Description Values Page
P5-03
(0D2E)
HAND/AUTO During
Run Selection
HAND/AUTO @ Run
0: Disabled
1: Enabled
Selects whether the drive will permit switching between HAND
and AUTO Modes while running.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
P5-04
(0D2F)
HAND Key Function
Selection
Oper HAND Key
0: Disabled
1: Enabled
Enables and disables the HAND key on the HOA keypad.
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
169
P5-05
(0D30)
HAND Reference 2 HAND Reference 2
Sets the frequency reference used when HAND Mode 2 is
active.
Default: 0.0 Hz
Min.: 0
Max.: [E1-04]
P5-06
(0D31)
HAND Ref. 1 Loss of
Prime Level
HandRef1 LOP Lvl
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
at the level set in P5-02, a “Loss of Prime” condition occurs.
The drive responds to the “Loss of Prime” condition depending
on the setting of P1-22, Loss of Prime Selection.
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 1000.0
P5-07
(0D32)
HAND Ref. 2 Loss of
Prime Level
HandRef2 LOP Lvl
Detects loss of prime in the pump.
When the measured quantity determined by P1-18 drops below
this level for the time set in P1-20 and the output frequency is
at the level set in P5-05, a “Loss of Prime” condition occurs.
The drive responds to the “Loss of Prime” condition depending
on the setting of P1-22, Loss of Prime Selection.
Default: 0.0 PSI
<1>
Min.: 0.0
Max.: 1000.0
P5-09
(0D34)
HAND References Set
via Motor Operated Pot
Selection
HAND MOP Sel
0: Disabled
1: Enabled
Selects whether parameters P5-02 and P5-05 are changed via
MOP from the home screen.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
<1> Unit text is set by P1-18, Prime Loss Detection Method.
u
P6: Flow Meter Setup
No.
(Addr.
Hex)
Name LCD Display Description Values Page
P6-01
(0D5E)
Flow Meter Scaling Flow Meter Scale
When an analog input is used for the flow rate, this parameter
performs the following functions:
Enables and disables flow meter functions. This parameter
must be set to a value greater than 0 to enable flow meter
functions.
Sets the scaling for the “Flow Rate” analog input.
Sets the scaling for the “Flow Rate” analog output.
Sets the display scaling when “Flow Rate” is used as the PID
feedback.
When an pulse input is used for the flow rate, this parameter
performs the following functions:
Enables and disables flow meter functions. Parameter must
be set to a value greater than zero to enable flow meter
functions.
Sets the scaling for the “Flow Rate” analog output.
Sets the display scaling when “Flow Rate” is used as the PID
feedback.
Default: 0.0
GPM
Min.: 0.0
Max.: 6000.0
P6-02
(0D5F)
Turbine Input Scaling
(Course)
Turbine Scale 1
Sets the scaling for the turbine in pulses per gallon.
Pulses/Gallon = P6-02 + P6-03
This parameter is internally lower-limited to 0.0001 ppG.
Default: 1 ppG
Min.: 0
Max.: 6000
P6-03
(0D60)
Turbine Input Scaling
(Fine)
Turbine Scale 2
Default: 0.0000
ppG
Min.: 0.0000
Max.: 0.9999
B.11 P: Pump Parameters
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
309