Name LCD Display Description Values Page
P6-18
(0D6F)
High Flow Detection
Delay Time
High Flow Time
Sets the length of time that the flow rate must be above the level
set in P6-17 to detect a High Flow condition.
Default: 10 s
Min.: 1
Max.: 6000
P6-19
(0D70)
High Flow Select
High Flow Sel
0: No Display
1: Alarm Only
2: Fault
3: Restart (L5-04)
Sets drive behavior when a High Flow condition is detected.
0: No display
1: Alarm only
2: Fault
3: Auto-restart (time set by L5-04)
Default: 1
Range: 0 to 3
<1> Unit text is set by P6-04, Water Flow Units.
<2> Unit text is set by P6-16, Flow Meter Accumulator Units Select.
u
P7: Anti-Jam
No.
(Addr.
Hex)
Name LCD Display Description Values Page
P7-01
(0D90)
Anti-Jam Operation
Selection
Anti-Jam Sel
0: Disabled
1: Enabled
Enables and disables the anti-jam function.
0: Disabled
1: Enabled
Default: 0
Range: 0, 1
P7-02
(0D91)
Anti-Jam Cycle Count AJ Cycle Count
Sets the maximum number of cycles that will be attempted
before triggering and Anti-Jam fault.
Default: 1
Min.: 1
Max.: 100
P7-03
(0D92)
Anti-Jam Detection
Current Level
AJ Det I @Start
Sets the current level at start that will trigger the anti-jam
function.
Set as a percentage of the motor rated current.
Default: 120%
Min.: 50
Max.: 200
P7-04
(0D93)
Anti-Jam Detection
Time at Start
AJ Det Tm@Start
Sets the length of time that current must rise above the level set
in P7-03 to trigger the anti-jam function.
Default: 0.3 s
Min.: 0.1
Max.: 2.0
P7-05
(0D94)
Anti-Jam During Run
Current
AJ Det I @Run
Sets the current level during run that will trigger the anti-jam
function.
Set as a percentage of motor rated current.
Setting this parameter to 0 will disable anti-jam during run.
Default: 0%
Min.: 0
Max.: 200
P7-06
(0D95)
Anti-Jam During Run
Time
AJ Det Tm @Run
Sets the length of time that the current must rise above the level
set in P7-05 to trigger the anti-jam function.
Restricted to simplex only.
Default: 0.3 s
Min.: 0.1
Max.: 2.0
P7-07
(0D96)
Anti-Jam Frequency
Reference
AJ Freq Ref
Sets the maximum speed allowed when the anti-jam function is
active.
Default: 25.00
Hz
Min.: 0.00
Max.: 400.00
P7-08
(0D98)
Anti-Jam Release Time AJ Release Time
Sets the length of time that the current must fall below the level
set in P7-03 to resume normal operation.
Default: 2.0 s
Min.: 0.5
Max.: 10.0
u
P9: Network Options
Parameters in this group are functional only when P1-01, Pump Mode, is set to 3 (MEMOBUS network).
No.
(Addr.
Hex)
Name LCD Display Description Values Page
P9-01
(0DF4)
Lead Drive Selection
Lead Drive Sel
0: Next Available
1: Lowest Runtime
2: Stop History
Specifies how the next lead drive is selected.
0: Next available
1: Lowest runtime
2: Stop history
Default: 1
Range: 0 to 2
P9-02
(0DF5)
Feedback Source
Feedback Source
0: Analog only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network only
Defines which signal to use for PI feedback when P1-01, Pump
Mode, is set to 3 (MEMOBUS network).
0: Analog only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network only
Default: 0
Range: 0 to 3
B.11 P: Pump Parameters
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
311
B
Parameter List