YASKAWA iQpump1000 - Appendix A Specifications

YASKAWA iQpump1000
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name LCD Display Description Values Page
P9-51
(0E26)
Low Water Level/
Suction Pressure Turn-
Off Method
Low WL Turn-Off
0: Disabled
1: Enabled
Determines the MEMOBUS multiplex response to Water Level
or Suction Pressure.
0: Disabled
Water level does not have an effect on Idle or Lag drives
Water level will not cause alternation
1: Enabled
A drive is considered offline when the Water Level/Suction
Pressure is below the wake-up level set in Q4-06/Q5-06.
A Lag drive is removed when the Water Level/Suction
Pressure is below the wake-up level set in Q4-06/Q5-06.
A Lead drive is alternated if in Level Control/Suction
Pressure while the Water Level is below the septoint set in
Q4-03/Q5-03.
Default: 0
Range: 0, 1
P9-60
(0E2F)
Geothermal
Temperature Source
Geo Temp Source
0: Analog only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network only
0: Analog only
1: Ana->Net, No Alrm
2: Ana->Net, Alarm
3: Network only
Default: 0
Range: 0 to 3
P9-99
(0E56)
Network Compatibility
Selection
Network Comp Sel
0: A-Ver: 30034
1: B-Ver: 30035/36
2: iQ SmartNetwork
Determines the communication compatibility for the iQPump
MEMOBUS network.
0: A-Ver: 30034
1: B-Ver: 30035/36
2: iQ SmartNetwork
Default: 2
Range: 0 to 2
<1> Unit text is set by P1-18, Prime Loss Detection Method.
B.11 P: Pump Parameters
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
315
B
Parameter List

Table of Contents