Name LCD Display Description Values Page
S2-05
(320A)
Sequence Timer 1
Reference Source
Tmr 1 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 1 is active (only applicable when
S2-04 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
S2-06
(320B)
Sequence Timer 2 Start
Time
Tmr 2 Start Time
Sets the start time for timer 2. The value must be set less than
or equal to S2-07.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
S2-07
(320C)
Sequence Timer 2 Stop
Time
Tmr 2 Stop Time
Sets the stop time for timer 2. The value must be set greater than
or equal to S2-06.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
S2-08
(320D)
Sequence Timer 2 Day
Selection
Tmr 2 Day Sel
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 2 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
S2-09
(320E)
Sequence Timer 2
Selection
Tmr 2 Seq Sel
0: Digital out only
1: Run
2: Run - PI Disable
Sets the action that occurs when sequence timer 2 is active.
0: Digital output only
1: Run
2: Run - PI disable
Default: 0
Range: 0 to 2
S2-10
(320F)
Sequence Timer 2
Reference Source
Tmr 2 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial com
6: Option PCB
7: Pulse Input
8: Set by b1-01
Selects the frequency reference source used for running the
drive when sequence timer 2 is active (only applicable when
S2-09 is set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
7: Pulse input
8: Set by b1-01
Default: 8
Range: 0 to 8
S2-11
(3210)
Sequence Timer 3 Start
Time
Tmr 3 Start Time
Sets the start time for timer 3. The value must be set less than
or equal to S2-12.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
S2-12
(3211)
Sequence Timer 3 Stop
Time
Tmr 3 Stop Time
Sets the stop time for timer 3. The value must be set greater than
or equal to S2-11.
Default: 00:00
Min.: 00:00
Max.: 24:00
<1>
S2-13
(3212)
Sequence Timer 3 Day
Selection
Tmr 3 Day Sel
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 3 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
S2-14
(3213)
Sequence Timer 3
Selection
Tmr 3 Seq Sel
0: Digital out only
1: Run
2: Run - PI Disable
Sets the action that occurs when sequence timer 3 is active.
0: Digital output only
1: Run
2: Run - PI disable
Default: 0
Range: 0 to 2
B.13 S: Special Application
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
321
B
Parameter List

Table of Contents