EasyManua.ls Logo

YASKAWA iQpump1000 - DRIVE WATT LOSS DATA

YASKAWA iQpump1000
356 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U1-12
(004B)
Drive Status Int Ctl Sts 1
Verifies the drive operation status.
U1
-
12=
00000000
During run
During zero-speed
During REV
During fault reset
signal input
During speed agree
Drive ready
During alarm
detection
During fault detection
1
1
1
1
1
1
1
1
No signal output
available
U1-13
(004E)
Terminal A1 Input
Level
Term A1 Level
Displays the signal level to analog input terminal A1.
10 V: 100% 0.1%
U1-14
(004F)
Terminal A2 Input
Level
Term A2 Level
Displays the signal level to analog input terminal A2.
10 V: 100% 0.1%
U1-15
(0050)
Terminal A3 Input
Level
Term A3 Level
Displays the signal level to analog input terminal A3.
10 V: 100% 0.1%
U1-16
(0053)
Output Frequency after
Soft Starter
SFS Output
Displays output frequency with ramp time and S-curves. Units
determined by o1-03.
10 V: Max
frequency
0.01 Hz
U1-18
(0061)
oPE Fault Parameter OPE Error Code
Displays the parameter number that caused the oPE02 operation
error.
No signal output
available
U1-19
(0066)
MEMOBUS/Modbus
Error Code
Transmit Err
Displays the contents of a MEMOBUS/Modbus error.
U1
-
19=
00000000
CRC Error
Data Length Error
Not Used
Parity Error
Overrun Error
Framing Error
Timed Out
Not Used
1
1
0
1
1
1
1
0
No signal output
available
U1-24
(007D)
Input Pulse Monitor Term RP Inp Freq
Displays the frequency to pulse train input terminal RP. Determined by
H6-02
1 Hz
U1-25
(004D)
Software Number
(Flash)
CPU 1 SW Number
FLASH ID No signal output
available
U1-26
(005B)
Software No. (ROM) CPU 2 SW Number
ROM ID No signal output
available
U1-75
(0851)
Time-Hour/Minute Time Hr Min HHMM
Displays the current time (Hours and Minutes). No signal output
available
U1-76
(0852)
Date – Year Date Year
Displays the current year. No signal output
available
U1-77
(0853)
Date – Month/Day Date Mo Day MMDD
Displays the current date (Month and Date). No signal output
available
U1-78
(0854)
Date – Week Day Date Week
Displays the current day of the week.
0: Sunday
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
No signal output
available
U1-80
(0B9B)
Geothermal
Temperature Input
Geothermal Temp
Displays the geothermal temperature input after the gain and
bias have been applied. This temperature is used by the
Geothermal Function to determine the proper frequency at
which to run the drive.
This monitor is internally limited to -999.9 °F to +999.9 °F.
No signal output
available
0.1 °F
B.15 U: Monitors
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
327
B
Parameter List

Table of Contents

Other manuals for YASKAWA iQpump1000

Related product manuals