Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
2A0030
R/L1, S/L2, T/L3 8 10 to 6
M4
2.1 to 2.3
(18.4 to 20.4)
U/T1, V/T2, W/T3 8 10 to 6
–, +1, +2 10 to 6
B1, B2 14 to 10
8
<1>
10 to 8 M5
2 to 2.5
(17.7 to 22.1)
2A0040
R/L1, S/L2, T/L3 6 8 to 6
M4
2.1 to 2.3
(18.4 to 20.4)
U/T1, V/T2, W/T3 8 8 to 6
–, +1, +2 6
B1, B2 12 to 10
8
<1>
10 to 8 M5
2 to 2.5
(17.7 to 22.1)
2A0056
R/L1, S/L2, T/L3 4 6 to 4
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2, W/T3 4 6 to 4
–, +1, +2 6 to 4
B1, B2 10 to 6 M5
2.7 to 3.0
(23.9 to 26.6)
6 8 to 6 M6
4 to 6
(35.4 to 53.1)
2A0069
R/L1, S/L2, T/L3 3 4 to 3
M8
9.9 to 11.0
(87.6 to 97.4)
U/T1, V/T2, W/T3 3 4 to 3
–, +1, +2 4 to 3
B1, B2 8 to 6 M5
2.7 to 3.0
(23.9 to 26.6)
6 6 to 4 M6
4 to 6
(35.4 to 53.1)
2A0081
R/L1, S/L2, T/L3 2 3 to 2
M8
9.9 to 11.0
(87.6 to 97.4)
U/T1, V/T2, W/T3 2 3 to 2
–, +1, +2 3 to 2
B1, B2 6 M5
2.7 to 3.0
(23.9 to 26.6)
6 6 to 4 M6
4 to 6
(35.4 to 53.1)
2A0110
<2>
R/L1, S/L2, T/L3 1/0 3 to 1/0
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3 1/0 3 to 1/0
–, +1 2 to 1/0
B1, B2 6 to 1/0
6 6 to 4
2A0138
<2>
R/L1, S/L2, T/L3 2/0 1 to 2/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 2/0 1 to 2/0
–, +1 1/0 to 3/0
B1, B2 4 to 2/0
4 4 M8
9 to 11
(79.7 to 97.4)
2A0169
<2>
R/L1, S/L2, T/L3 4/0 2/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 4/0 3/0 to 4/0
–, +1 1 to 4/0
+3 1/0 to 4/0
4 4 to 2
2A0211
<2>
R/L1, S/L2, T/L3 1/0 × 2P 1/0 to 2/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 1/0 × 2P 1/0 to 2/0
–, +1 1 to 4/0
+3 1/0 to 4/0
4 4 to 1/0
3.6 Main Circuit Wiring
88
YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide