Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model
Number
Tool
Insulation
Cap Model
No.
Code
<1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 Machine No. Die Jaw
4A1200
4/0 × 8P
M12
100-L12
YF-1
YET-300-1
TD-324,
TD-312
TP-100 100-051-560
250 × 8P
150-L12
TD-325,
TD-313
TP-150 100-051-562
300 × 8P
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
Factory Recommended Branch Circuit Protection for UL Compliance
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral devices.
Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral
devices if the cause cannot be identified.
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with UL508C.
Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in the tables
below.
Table i.27 Factory Recommended Drive Branch Circuit Protection (Normal Duty)
Drive Model
Normal Duty
Nominal
Output Power
HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay
Fuse Rating
Amps
<3>
Bussmann Semi-
conductor Fuse
Rating (Fuse
Ampere)
<4>
200 V Class
2A0004 0.75 3.9 15 6.25 10 FWH-70B (70)
2A0006 1 - 1.5 7.3 15 12 20 FWH-70B (70)
2A0008 2 8.8 15 15 25 FWH-70B (70)
2A0010 3 10.8 20 17.5 30 FWH-70B (70)
2A0012 3 13.9 25 20 40 FWH-70B (70)
2A0018 5 18.5 35 30 50 FWH-90B (90)
2A0021 7.5 24 45 40 70 FWH-90B (90)
2A0030 10 37 60 60 110 FWH-100B (100)
2A0040 15 52 100 90 150 FWH-200B (200)
2A0056 20 68 125 110 200 FWH-200B (200)
2A0069 25 80 150 125 225 FWH-200B (200)
2A0081 30 96 175 150 275 FWH-300A (300)
2A0110 40 111 200 175 300 FWH-300A (300)
2A0138 50 136 250 225 400 FWH-350A (350)
2A0169 60 164 300 250 450 FWH-400A (400)
2A0211 75 200 400 350 600 FWH-400A (400)
2A0250 100 271 500 450 800 FWH-600A (600)
2A0312 125 324 600 500 800 FWH-700A (700)
2A0360 150 394 700 600
1000
<5>
FWH-800A (800)
2A0415 175 471 900 800
1400
<5>
FWH-1000A (1000)
400 V Class
4A0002 1 2.1 15 3.5 6 FWH-40B (40)
4A0004 2 4.3 15 7.5 12 FWH-50B (50)
4A0005 3 5.9 15 10 17.5 FWH-70B (70)
i.9 Standards Compliance
YASKAWA TOEP YAIP1W 02E YASKAWA AC Drive - iQpump1000 Installation & Start-up Guide
107