EasyManua.ls Logo

YASKAWA iQpump1000 - Mechanical Installation

YASKAWA iQpump1000
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
n
Input Terminals
Table i.7 lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.
Table i.7 Control Circuit Input Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting
Multi-Function
Digital Inputs
S1
Multi-function input 1
(Closed: Forward run, Open: Stop)
Photocoupler
24 Vdc, 8 mA
Refer to Sinking/Sourcing Mode for Digital Inputs on page 40.
S2
Multi-function input 2
(Through mode)
S3
Multi-function input 3
(External pump fault, N.O.)
S4
Multi-function input 4
(Fault reset)
S5
Multi-function input 5
(Multi setpoint 1)
S6
Multi-function input 6
(HAND mode)
S7
Multi-function input 7
(HAND mode 2)
S8
Multi-function input 8
(Through mode)
SC Multi-function input common Multi-function input common
SP Digital input power supply +24 Vdc 24 Vdc power supply for digital inputs, 150 mA max
NOTICE: Do not jumper or short terminals SP and SN. Failure to
comply will damage the drive.
SN
Digital input power supply 0 V
24 V transducer power supply 0 V
Analog Inputs /
Pulse Train
Input
RP
Multi-function pulse train input
(Frequency reference)
Input frequency range: 0 to 32 kHz
Signal Duty Cycle: 30 to 70%
High level: 3.5 to 13.2 Vdc, low level: 0.0 to 0.8 Vdc
Input impedance: 3 kΩ
+V Power supply for analog inputs 10.5 Vdc (max allowable current 20 mA)
24 V +24 Vdc transducer power supply for customer use 150 mA maximum capacity
A1
Multi-function analog input 1
(Frequency reference bias)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Voltage or current input must be selected by jumper S1 and H3-01.
A2
Multi-function analog input 2
(PID feedback)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Voltage or current input must be selected by jumper S1 and H3-09.
A3
Multi-function analog input 3
(HAND frequency reference)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
4 to 20 mA, 0 to 20 mA (input impedance: 250 Ω)
Voltage or current input must be selected by jumper S1 and H3-05.
AC Frequency reference common 0 V
E (G) Ground for shielded lines and option cards
n
Output Terminals
Table i.8 lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.
Table i.8 Control Circuit Output Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting
Fault Relay
Output
MA N.O.
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
MB N.C. output
MC Fault output common