HOA Keypad Display Alarm Name
Low Water in Tank Low Water in Tank
Low WL/SP/PI-Aux Drive Disabled
Low Water Level / Suction Pressure / Aux PI Feedback Disabled
Water Level or Suction Pressure is below the Q4-06/Q5-06/Q6-06 setting.
LT-1
Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.
Note:
An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F and H2-oo = 10) are
set.
LT-2
Capacitor Maintenance Time
The main circuit and control circuit capacitors are nearing the end of their expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
LT-3
Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
LT-4
IGBT Maintenance Time (50%)
IGBTs have reached 50% of their expected performance life.
Note:
An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.
Main FdBk Lost
Using Backup FB
Main PI Feedback Lost
Main FdBk Lost
Using Backup FB
Main Feedback Device (H3-oo = B) lost.
Net Flow Meter
Lost, Chk Source
Net Flow Meter Loss
There is no drive on the MEMOBUS network with an analog flow meter.
NETSCAN
Waiting for Master
NETSCAN
Drive is waiting for a message from the master.
NMS
Not Maintaining Setpoint
The setpoint cannot be maintained and P1-17 is set to 1.
oH
Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02.
oH2
Drive Overheat Warning
“Drive Overheat Warning” was input to a multi-function input terminal, S1 through S8 (H1-oo= B).
oH3
Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level (H3-02, H3-06
or H3-10 = E).
oH5
<1>
Motor Overheat (NTC Input)
The motor temperature exceeded the level set to L1-16 (or L1-18 for motor 2)
oL1
Motor Overload
The electronic motor overload protection tripped
oL2
Drive Overload
The thermal sensor of the drive triggered overload protection.
oL3
Overtorque Detection 1
The current has exceeded the value set for torque detection (L6-02) for longer than the allowable time (L6-03).
oL4
Overtorque Detection 2
The current has exceeded the value set for Overtorque Detection 2 (L6-05) for longer than the allowable time
(L6-06).
ov
DC Bus Overvoltage
The DC bus voltage exceeded the trip point.
For 200 V class drives: approximately 410 V
For 400 V class drives: approximately 820 V (740 V when E1-01 is less than 400)
For 600 V class drives: approximately 1040 V
PoC Pump Over Cycle
R-DNE-So
Remote Drive Disable
i.6 Troubleshooting
80