No.
(Addr.
Hex)
Name LCD Display Description Values Page
F7-15
(03F3)
Communication Speed
Selection
Baud Rate
10: 10 Mbps
100: 100 Mbps
Sets the communication speed
10: 10 Mbps
100: 100 Mbps
Default: 10
Range: 10, 100
–
F7-16
(03F4)
Communication Loss
Timeout
CommLoss Tout
Sets the timeout value for communication loss detection in
tenths of a second. A value of 0 disables the connection timeout.
Example: An entered value of 100 represents 10.0 seconds.
Default: 0
Min.: 0
Max.: 300
–
F7-17
(03F5)
EtherNet/IP Speed
Scaling Factor
EN Speed Scale
Sets the scaling factor for the speed monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-18
(03F6)
EtherNet/IP Current
Scaling Factor
EN Current Scale
Sets the scaling factor for the output current monitor in
EtherNet/IP Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-19
(03F7)
EtherNet/IP Torque
Scaling Factor
EN Torque Scale
Sets the scaling factor for the torque monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-20
(03F8)
EtherNet/IP Power
Scaling Factor
EN Power Scale
Sets the scaling factor for the power monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-21
(03F9)
EtherNet/IP Voltage
Scaling Factor
EN Voltage Scale
Sets the scaling factor for the voltage monitor in EtherNet/IP
Class ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-22
(03FA)
EtherNet/IP Time
Scaling
EN Time Scale
Sets the scaling factor for the time monitor in EtherNet/IP Class
ID 2AH Object.
Default: 0
Min.: -15
Max.: 15
–
F7-23 to
F7-32
(03FB to
0374)
Dynamic Output
Assembly Parameters
–
Parameters used in Output Assembly 116. Each parameter
contains a MEMOBUS/Modbus address. The value received for
Output Assembly 116 will be written to this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value received for Output Assembly
116 will not be written to any MEMOBUS/Modbus register.
Default: 0 –
F7-33 to
F7-42
(0375 to
037E)
Dynamic Input
Assembly Parameters
–
Parameters used in Input Assembly 166. Each parameter
contains a MEMOBUS/Modbus address. The value sent for
Input Assembly 166 will be read from this corresponding
MEMOBUS/Modbus address. A MEMOBUS/Modbus address
value of 0 means that the value sent for Input Assembly 166 is
not defined by the user, therefore the option default register
value will be returned.
Default: 0 –
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Values shown are for the MECHATROLINK-II option (SI-T3). Values for MECHATROLINK-III option (SI-ET3) are:
Min: 03
Max.: EF
<3> Values shown are for the MECHATROLINK-II option (SI-T3). Values for MECHATROLINK-III option (SI-ET3) are:
0: 64-byte
1: 32-byte
<4> Cycle power for setting changes to take effect.
<5> If F7-13 is set to 0, all IP addresses (F7-01 to F7-04) must be unique.
B.7 F: Options
372