Standards Compliance
5
5.2 European Standards
YASKAWA SIEPYEULA5001C LA500 Technical Manual 123
A - Braided shield cable
B - Metal plate
C - Cable clamp (conductive)
Figure 5.11 Ground the Shield
A - Grounding surface (Remove any paint or
sealant.)
B - Enclosure panel
C - Metal plate
D - Drive
E - Ground the shield.
F - Motor
G - Motor cable (Braided shield cable: 10 m (32.8 ft)
maximum)
H - Cable clamp
I - Grounding wire
J - EMC noise filter
Figure 5.12 EMC Noise Filter and Drive Installation Procedure
5. Connect the DC reactor to decrease harmonic distortion.
Ground Wiring
WARNING! Electrical Shock Hazard. Do not remove covers or touch circuit boards while the drive is energized. If you touch the
internal components of an energized drive, it can cause serious injury or death.