Specifications
10
10.3 Drive Specifications
YASKAWA SIEPYEULA5001C LA500 Technical Manual 227
Item Specification
Momentary Power
Loss Ride-thru
Stops when power loss is longer than 15 ms and continues operation if power loss is shorter than 2 s (depending on parameter settings).
Note:
• Load size and motor speed can cause the stop time to be shorter.
• Drive capacity will change the continuous operation time. A Momentary Power Loss Recovery Unit is necessary to continue operation through a 2 s
power loss on models 4009 to 4018.
Heatsink Overheat
Protection
Thermistor
Stall Prevention
Stall prevention is available during acceleration, deceleration, and during run.
Ground Fault
Protection
Electronic circuit protection
Note:
This protection detects ground faults during run. The drive will not provide protection when:
• There is a low-resistance ground fault for the motor cable or terminal block
• Energizing the drive when there is a ground fault.
DC Bus Charge LED
Charge LED illuminates when DC bus voltage is more than 50 V.
Table 10.5 Environment
Item Specification
Area of Use
Indoors
Power Supply
Overvoltage Category III
Ambient
Temperature Setting
IP20/UL Open Type: -10°C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
• When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
• Do not let the drive freeze.
Humidity
95% RH or less
Do not let condensation form on the drive.
Storage Temperature
-20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Surrounding Area
Pollution degree 2 or less
Install the drive in an area without:
• Oil mist, corrosive or flammable gas, or dust
• Metal powder, oil, water, or other unwanted materials
• Radioactive materials or flammable materials, including wood
• Harmful gas or fluids
• Salt
• Direct sunlight
Altitude
1000 m (3281 ft) Maximum
Note:
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 m to 4000 m (3281 ft to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
• Installing the drive at 2000 m (6562 ft) or lower
• Installing the drive between 2000 m to 4000 m (6562 ft to 13123 ft) and grounding the neutral point on the power supply.
Contact Yaskawa or your nearest sales representative when not grounding the neutral point.
Vibration
• 10 Hz to 20 Hz: 1 G (9.8 m/s
2
, 32.15 ft/s
2
)
• 20 Hz to 55 Hz: 0.6 G (5.9 m/s
2
, 19.36 ft/s
2
)
Installation
Orientation
Install the drive vertically for sufficient airflow to cool the drive.
Table 10.6 Standard
Item Specification
Harmonized Standard
• UL 61800-5-1
• EN 61800-3
• EN 61800-5-1
• Two Safe Disable inputs and one EDM output according to EN ISO 13849-1 (Cat.3, PL e), EN 61800-5-2 SIL3
Enclosure protection
design
IP20/UL Open Type
IP20/UL Type 1
Note:
Install a UL Type 1 kit (optional) on an IP20/UL Open Type drive to change the drive to an IP20/UL Type 1 enclosure.