7-13
168542-1CD
168542-1CD
MLX200 Software and
Operations
7 Configuration and Maintenance of MLX200 Control Module
7.2 Maintenance and Configuration Operations
Click on the [Execute] button after selecting the appropriate backup
operation. The backed up files will be written to folder on the USB Disk
with the folder name including a time stamp of the operation. The folder
name used for the operation will be displayed in the message box area
towards the bottom of the screen.
The procedure to restore the firmware from a backup or restore all Control
Module files from backup is similar. Click on the “Upload/Restore”
category on the left in the {Maintenance Operations} screen, and select
the appropriate restore operation as shown in Fig.7-19 "Selecting a
Restore Operation".
Fig. 7-19: Selecting a Restore Operation
Click on the [Execute] button after selecting the appropriate restore
operation. A new pop-up dialog will be shown as shown in Fig.7-20
"Selecting the Folder Containing Backed Up Files to Restore" that allows
the user the select the folder in the USB disk that contains the backed up
files to be used for the restore operation.
Fig. 7-20: Selecting the Folder Containing Backed Up Files to Restore
Performing a backup operation is not permitted when the
MLX200 PLC Interface software (MLX-R.exe) is currently
running. Before attempting to perform the backup operation,
please ensure that the PLC Interface Application is not
running through the procedure described in Section 7.2.9.1
“Disabling Automatic Restart of MLX-R.exe”.