Alarm Code Alarm Name Possible Cause Confirmation Correction Reference
A.d02
(1d02h)
Position Devia-
tion Overflow
Alarm for Speed
Limit at Servo
ON
If position deviation
remains in the devia-
tion counter, the set-
ting of Pn529 or
Pn584 (Speed Limit
Level at Servo ON)
limits the speed when
the servo is turned
ON. This alarm occurs
if a position reference
is input and the set-
ting of Pn520 (Exces-
sive Position Devia-
tion Alarm Level) is
exceeded.
Optimize the setting
of Pn520. Or, set
Pn529 or Pn584 to
an appropriate value.
A.d10
(1d10h)
Motor-Load
Position Devia-
tion Overflow
The motor direction
and external encoder
installation orientation
are backward.
Check the motor
direction and the
external encoder
installation orienta-
tion.
Install the external
encoder in the oppo-
site direction, or
change the setting of
Pn002 = n.X
(External Encoder
Usage) to reverse
the direction.
Ä
Chap. 11.4.3
‘Setting the
Motor Direction
and the
Machine Move-
ment Direction’
page 458
There is an error in
the connection
between the load
(e.g., stage) and
external encoder cou-
pling.
Check the coupling
of the external
encoder.
Check the mechan-
ical coupling.
A.d30
(1d30h)
Position Data
Overflow
The position data
exceeded
±1,879,048,192.
Check the input ref-
erence pulse
counter.
Reconsider the oper-
ating specifications.
A.E00
(1E00h)
PROFINET
Module Inter-
face Initializa-
tion Timeout
Error
A failure occurred in
the SERVOPACK.
Replace the SERVO-
PACK.
A.E02
(1E02h)
PROFINET
Internal Syn-
chronization
Error 1
The PROFINET trans-
mission cycle fluctu-
ated.
Remove the cause of
transmission cycle
fluctuation at the
host controller.
A failure occurred in
the SERVOPACK.
Turn the power
supply to the SER-
VOPACK OFF and
ON again. If an
alarm still occurs, the
SERVOPACK may
be faulty. Replace
the SERVOPACK.
A.E03
(1E03h)
PROFINET
Module Inter-
face Communi-
cations Data
Error
Noise caused an error
in communications
between the SERVO-
PACK and PROFINET
Network Module.
Implement counter-
measures against
noise.