Status Description
Open Output frequency is more than or equal to the minimum output frequency set to E1-09 or b2-01
Closed Output frequency becomes less than the minimum output frequency set to E1-09 or b2-01
Note: When using CLV or CLV/PM control modes, the output terminal closes when the motor speed becomes less than or equal to the zero speed
level set for b2-01. In all other control modes, the output terminal closes when the output frequency becomes less than or equal to the
minimum output frequency set for E1-09.
OFF
Output frequency
Zero Speed
ON
E1-09 (Min. Output Frequency) or
b2-01 (Zero Speed Level)
Figure 5.67 Zero-Speed Time Chart
Setting 2: Speed Agree 1 (f
ref
/f
out
Agree 1)
Closes when the actual output frequency or motor speed (CLV, CLV/PM) is within the Speed Agree Width (L4-02) of the
current frequency reference regardless of the direction.
Status Description
Open Output frequency or motor speed is outside the range of frequency reference ±L4-04.
Closed Output frequency or motor speed is within the range of frequency reference ±L4-02.
Note: Detection works in forward and reverse.
L4-04
L4-04
Frequency
reference
Speed Agree 2
ON
OFF
ON
OFF
Output Frequency or
Motor Speed
Figure 5.68 Speed Agree 1 Time Chart
Refer to L4-01, L4-02: Speed Agree Detection Level and Detection Width on page 320 for more details.
Setting 3: User-Set Speed Agree 1 (f
ref
/f
set
Agree 1)
Closes when the actual output frequency or motor speed (CLV, CLV/PM) and the frequency reference are within the speed
agree width (L4-02) of the programmed speed agree level (L4-01).
Status Description
Open Output frequency or motor speed and frequency reference are not both within the range of L4-01 ±L4-02.
Closed Output frequency or motor speed and the frequency reference are both within the range of L4-01 ±L4-02.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
5.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
289
5
Parameter Details