Three-Phase 400 V Class Drive Models 4o0477 to 4o0930
Table A.6 Power Ratings (Three-Phase 400 V Class) Continued
Item Specification
Drive Model
4o0477 4o0590 4o0720 4o0900 4o0930
Maximum Applicable Motor Capacity kW
(HP)
<1>
HD Rating 260 (350) 300 (400) 375 (500) 450 (600) 560 (750)
ND Rating 300 (400) 375 (500) 450 (600) 560 (750) 580 (775)
Input/
Output
Rating
Rated Input
Current (A)
<2>
HD Rating 377 434 537 655 819
ND Rating 434 537 655 819 846
Rated Input
Capacity (kVA)
<3>
HD Rating 344 396 490 598 748
ND Rating 396 490 598 748 773
Rated Output
Current (A)
<4>
HD Rating 414 477 590 720 900
ND Rating 477 590 720 900 930
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency 3 kHz
Maximum Output Voltage (V)
Proportional to input voltage
<5>
Maximum Output Frequency (Hz) 400 Hz (User-adjustable)
Power
Supply
Rated Voltage
Rated Frequency
Three-phase 4Aoooo and 4Poooo 380 to 500 Vac
<6>
50/60 Hz
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply
Voltage Unbalance
2% or less
Harmonic Current Distortion
<5>
5% or less (IEEE519 compliant)
Input Power Factor 0.98 or more (During rated operation)
<1> The motor capacity (HP) refers to an NEC 4-pole motor. The rated output current of the drive should be equal to or greater than the motor current.
Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated input capacity is calculated with a power line voltage of 480 V × 1.1.
<4> The rated output current of the drive should be equal to or greater than the motor rated current.
<5> Commercial power mode results in near zero input harmonics. Existing power conditions and operation mode can affect input harmonics.
<6> Use a stand-alone EMC filter with a voltage of 380 to 480 V.
A.2 Power Ratings
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
481