B.17 V/f Pattern Default Values
Table B.6 to Table B.8 show the V/f pattern setting default values depending on the control mode and V/f pattern selection
(A1-02 and E1-03).
Table B.6 E1-03 V/f Pattern Settings for Drive Capacity: Models 4o0011 and 4o0014
No. Unit V/f Control
OLV CLV
E1-03 - 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<1>
E1-04
Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 60.0 60.0 60.0
E1-05
<2>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 230.0 230.0 230.0
E1-06
Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 –
E1-07
Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 –
E1-08
<2>
V 15.0 15.0 15.0 15.0 35.0 50.0 35.0 50.0 19.0 24.0 19.0 24.0 15.0 15.0 15.0 17.3 13.8 –
E1-09
Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5 0.5 –
E1-10
<2>
V 9.0 9.0 9.0 9.0 8.0 9.0 8.0 9.0 11.0 13.0 11.0 15.0 9.0 9.0 9.0 10.2 2.9 –
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
Table B.7 E1-03 V/f Pattern Settings for Drive Capacity: Models 2o0028 to 2o0192 and 4o0021 to 4o0124
No. Unit V/f Control
OLV CLV
E1-03 - 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<1>
E1-04
Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 60.0 60.0 60.0
E1-05
<2>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 230.0 230.0 230.0
E1-06
Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 –
E1-07
Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 –
E1-08
<2>
V 14.0 14.0 14.0 14.0 35.0 50.0 35.0 50.0 18.0 23.0 18.0 23.0 14.0 14.0 14.0 16.1 12.7 –
E1-09
Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5 0.5 –
E1-10
<2>
V 7.0 7.0 7.0 7.0 6.0 7.0 6.0 7.0 9.0 11.0 9.0 13.0 7.0 7.0 7.0 8.1 2.3 –
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
Table B.8 E1-03 V/f Pattern Settings for Drive Capacity: Models 2o0248 and 4o0156 to 4o0930
No. Unit V/f Control
OLV CLV
E1-03 - 0 1 2 3 4 5 6 7 8 9 A B C D E
F
<1>
E1-04 Hz 50.0 60.0 60.0 72.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 90.0 120.0 180.0 60.0 60.0 60.0
E1-05
<2>
V 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 200.0 230.0 230.0 230.0
E1-06
Hz 50.0 60.0 50.0 60.0 50.0 50.0 60.0 60.0 50.0 50.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 –
E1-07
Hz 2.5 3.0 3.0 3.0 25.0 25.0 30.0 30.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 –
E1-08
<2>
V 12.0 12.0 12.0 12.0 35.0 50.0 35.0 50.0 15.0 20.0 15.0 20.0 12.0 12.0 12.0 13.8 12.7 –
E1-09
Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5 0.5 –
E1-10
<2>
V 6.0 6.0 6.0 6.0 5.0 6.0 5.0 6.0 7.0 9.0 7.0 11.0 6.0 6.0 6.0 6.9 2.3 –
<1> This value determines the default values for E1-04 through E1-10 (E3-04 through E3-10 for motor 2).
<2> Values shown here are specific to 200 V class drives. Double the value for 400 V class drives.
B.17 V/f Pattern Default Values
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
587