B.18 Defaults by Drive Model and Duty Rating ND/HD
The following tables show parameters and default settings that change with the drive model selection (o2-04) and drive duty
selection (C6-01). Parameter numbers shown in parenthesis are valid for motor 2.
Table B.9 200 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No. Name Unit Default Settings
– Drive Model –
2o0028 2o0042 2o0054 2o0068
C6-01 Drive Duty Selection – HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. 6A 6B 6D 6E
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
5.5 (7.5) 7.5 (10) 7.5 (10) 11 (15) 11 (15) 15 (20) 15 (20) 18.5 (25)
b3-04 V/f Gain during Speed Search % 100 100 100 100 100 100 100 100
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
– 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value – 94.75 72.69 72.69 70.44 70.44 63.13 63.13 57.87
C5-17 (C5-37) Motor Inertia
kgm
2
0.026 0.037 0.037 0.053 0.053 0.076 0.076 0.138
C6-02 Carrier Frequency Selection – 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 19.6 26.6 26.6 39.7 39.7 53 53 65.8
E2-02 (E4-02) Motor Rated Slip Hz 1.5 1.3 1.3 1.7 1.7 1.6 1.6 1.67
E2-03 (E4-03) Motor No-Load Current A 5.1 8 8 11.2 11.2 15.2 15.2 15.7
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.399 0.288 0.288 0.23 0.23 0.138 0.138 0.101
E2-06 (E4-06) Motor Leakage Inductance % 18.2 15.5 15.5 19.5 19.5 17.2 17.2 20.1
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 172 262 262 245 245 272 272 505
E5-01 Motor Code Selection (for PM Motors) Hex. 120A 120A 120B 120B 120D 120D 120E 120E
L2-02 Momentary Power Loss Ride-Thru Time s 0.7 0.8 0.8 0.9 0.9 1 1 1
L2-03
Momentary Power Loss Minimum
Baseblock Time
s 0.3 0.3 0.3 0.3 0.3 0.6 0.6 0.6
L2-04
Momentary Power Loss Voltage Recovery
Time
s 150 150 150 150 150 150 150 150
L2-21 Low Input Voltage Detection Level V 150 150 150 150 150 150 150 150
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection – 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.168 0.175 0.175 0.265 0.265 0.244 0.244 0.317
Table B.10 200 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No. Name Unit Default Settings
– Drive Model –
2o0081 2o0104 2o0130 2o0154
C6-01 Drive Duty Selection – HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. 6F 70 72 73
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
18.5 (25) 22 (30) 22 (30) 30 (40) 30 (40) 37 (50) 37 (50) 45 (60)
b3-04 V/f Gain during Speed Search % 100 100 100 80 80 80 80 80
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
– 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04 Energy Saving Coefficient Value – 57.87 51.79 51.79 46.27 46.27 38.16 38.16 35.78
C5-17 (C5-37) Motor Inertia
kgm
2
0.138 0.165 0.165 0.220 0.220 0.273 0.273 0.333
C6-02 Carrier Frequency Selection – 1 1 1 1 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 65.8 77.2 77.2 105 105 131 131 160
E2-02 (E4-02) Motor Rated Slip Hz 1.67 1.7 1.7 1.8 1.8 1.33 1.33 1.6
B.18 Defaults by Drive Model and Duty Rating ND/HD
588