No. Name Unit Default Settings
– Drive Model –
2o0081 2o0104 2o0130 2o0154
C6-01 Drive Duty Selection – HD ND HD ND HD ND HD ND
o2-04 Drive Model Selection Hex. 6F 70 72 73
E2-11
(E4-11)
Motor Rated Output
kW
(HP)
18.5 (25) 22 (30) 22 (30) 30 (40) 30 (40) 37 (50) 37 (50) 45 (60)
E2-03 (E4-03) Motor No-Load Current A 15.7 18.5 18.5 21.9 21.9 38.2 38.2 44
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.101 0.079 0.079 0.064 0.064 0.039 0.039 0.03
E2-06 (E4-06) Motor Leakage Inductance % 20.1 19.5 19.5 20.8 20.8 18.8 18.8 20.2
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 505 538 538 699 699 823 823 852
E5-01 Motor Code Selection (for PM Motors) Hex. 120F 120F 1210 1210 1212 1212 1213 1213
L2-02 Momentary Power Loss Ride-Thru Time s 1 1 1 1.1 1.1 1.1 1.1 1.2
L2-03
Momentary Power Loss Minimum
Baseblock Time
s 0.6 0.6 0.6 0.6 0.6 0.6 0.6 1
L2-04
Momentary Power Loss Voltage Recovery
Time
s 150 150 150 150 150 150 150 150
L2-21 Low Input Voltage Detection Level V 150 150 150 150 150 150 150 150
L8-02 Overheat Alarm Level °C 130 130 130 130 130 130 130 130
L8-35 Installation Method Selection – 0 0 0 0 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10 10 10 10 10
n5-02 Motor Acceleration Time s 0.317 0.355 0.355 0.323 0.323 0.32 0.32 0.387
Table B.11 200 V Class Drives Default Settings by Drive Model Selection and ND/HD Settings
No. Name Unit Default Settings
– Drive Model –
2o0192 2o0248
C6-01 Drive Duty Selection – HD ND HD ND
o2-04 Drive Model Selection Hex. 74 75
E2-11 (E4-11) Motor Rated Output kW (HP) 45 (60) 55 (75) 55 (75) 75 (100)
b3-04 V/f Gain during Speed Search % 80 80 80 80
b3-06 Output Current 1 during Speed Search – 0.5 0.5 0.5 0.7
b3-08
Current Control Gain during Speed Search
(Speed Estimation Type)
– 0.5 0.5 0.5 0.5
b8-03 Energy Saving Control Filter Time Constant s 0.50 2.00 2.00 2.00
b8-04 Energy Saving Coefficient Value – 35.78 31.35 31.35 23.1
C5-17 (C5-37) Motor Inertia
kgm
2
0.333 0.490 0.490 0.900
C6-02 Carrier Frequency Selection – 1 1 1 1
E2-01 (E4-01) Motor Rated Current A 160 190 190 260
E2-02 (E4-02) Motor Rated Slip Hz 1.6 1.43 1.43 1.39
E2-03 (E4-03) Motor No-Load Current A 44 45.6 45.6 72
E2-05 (E4-05) Motor Line-to-Line Resistance Ω 0.03 0.022 0.022 0.023
E2-06 (E4-06) Motor Leakage Inductance % 20.2 20.5 20.5 20
E2-10 (E4-10) Motor Iron Loss for Torque Compensation W 852 960 960 1200
E5-01 Motor Code Selection (for PM Motors) Hex. 1214 1214 1215 1215
L2-02 Momentary Power Loss Ride-Thru Time s 1.2 1.3 1.3 1.5
L2-03 Momentary Power Loss Minimum Baseblock Time s 1 1 1 1
L2-04 Momentary Power Loss Voltage Recovery Time s 150 150 150 150
L2-21 Low Input Voltage Detection Level V 150 150 150 150
L8-02 Overheat Alarm Level °C 130 130 130 130
L8-35 Installation Method Selection – 0 0 0 0
L8-38 Carrier Frequency Reduction Selection – 1 1 1 1
n1-03 Hunting Prevention Time Constant ms 10 10 10 10
n5-02 Motor Acceleration Time s 0.387 0.317 0.317 0.533
B.18 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
589
B
Parameter List