Register No. Contents
00DCH
oFb0o Contents (CN5-B)
bit 0 Option compatibility error (oFb00)
bit 1 Option not properly connected (oFb01)
bit 2 Same type of option card already connected (oFb02)
bit 3, 4 Reserved
bit 5 A/D Conversion Fault (oFb05)
bit 6 Option Response Error (oFb06)
bit 7 to F Reserved
00DDH
oFb1o Contents (CN5-B)
bit 0 Option RAM Fault (oFb10)
bit 1 Option Operation Mode Fault (SLMOD) (oFb11)
bit 2 Unit Receive CRC Error (oFb12)
bit 3 Unit Receive Frame Error (oFb13)
bit 4 Unit Receive Abort Error (oFb14)
bit 5 Option Receive CRC Error (oFb15)
bit 6 Option Receive Frame Error (oFb16)
bit 7 Option Receive Abort Error (oFb17)
bit 8 to F Reserved
00DEH to 00DFH Reserved
00E0H
oFb3o Contents (CN5-B)
bit 0 Comm. ID Error (oFb30)
bit 1 Model Code Error (oFb31)
bit 2 Sumcheck Error (oFb32)
bit 3 Comm. option timeout waiting for response (oFb33)
bit 4 MEMOBUS Timeout (oFb34)
bit 5 Unit timeout waiting for response (oFb35)
bit 6 CI Check Error (oFb36)
bit 7 Unit timeout waiting for response (oFb37)
bit 8 Control Command Selection Error (oFb38)
bit 9 Unit timeout waiting for response (oFb39)
bit A Control Response Selection 1 Error (oFb40)
bit B Unit timeout waiting for response (oFb41)
bit C Control Response Selection 2 Error (oFb42)
bit D Control Response Selection Error (oFb43)
bit E, F Reserved
00E1H
oFC0o Contents (CN5-C)
bit 0 Option compatibility error (oFC00)
bit 1 Option not properly connected (oFC01)
bit 2 Same type of option card already connected (oFC02)
bit 3, 4 Reserved
bit 5 A/D Conversion Fault (oFC05)
bit 6 Option Response Error (oFC06)
bit 7 to F Reserved
C.9 MEMOBUS/Modbus Data Table