Subfield Parameter
ID Type Length
(byte)
Description Special features Use
15 SUB_CLIENT_ID Length
Client-ID + 4
- - optional
51 MAC-ADR 4 + 6 MAC address local
node
optional
There is shown below which values are needed to be entered in the parameter fields and
which subfields are to be used for the various connection types. Some applications do not
require all the subfield types. The ID parameter that precedes each connection parameter
field beside the type ID is particularly important. On programmed connections this ID may
freely be assigned within the permitted range of values. For identification of the connec-
tion this ID is to be used on the call interface of the FCs for the SEND/RECV.
Range of values for the connection ID: 1, 2 ... 64
Subfield Parameter
ID Type Length (byte) Description Special features Use
1 SUB_IP_V4 4 + 4 IP address of the remote station
according to IPv4
mandatory
1
9 SUB_LOC_PORT 4 + 2 Port of the local station mandatory
10 SUB_REM_PORT 4 + 2 Port of the remote station
mandatory
1
18 SUB_CONNECT_NAME Length Name
+ 4
Name of the connection optional
19 SUB_LOC_MODE 4 + 1 Local mode of the connection,
Possible values:
0x00 = SEND/REC
0x10 = S5-addressing mode for FETCH/
WRITE
2
0x80 = FETCH
2
0x40 = WRITE
2
If you do not set the parameter, the
default setting is SEND/RECV.
For FETCH/WRITE a passive connection
setup is necessary.
optional
21 SUB_KBUS_ADR - - Value: fix 2 optional
Parameter fields for Con-
nections
TCP connection
VIPA SPEED7
Network Communication
Ethernet Communication > FB 55 - IP_CONF - Progr. Communication Connections