Name Declara-
tion
Type Description
FC1_ADDR_OUTPUT_END STAT WORD Modbus Function code 01h end register for Qx.y
Default: 19999
FC1_ADDR_MEMORY_START STAT WORD Modbus Function code 01h start register for M0.0
Default: 20000
FC1_ADDR_MEMORY_END STAT WORD Modbus Function code 01h end register for Mx.y
Default: 39999
FC2_ADDR_INPUT_START STAT WORD Modbus Function code 02h start register for I0.0
Default: 0
FC2_ADDR_INPUT_END STAT WORD Modbus Function code 02h end register for Ix.y
Default: 19999
FC2_ADDR_MEMORY_START STAT WORD Modbus Function code 02h start register for M0.0
Default: 20000
FC2_ADDR_MEMORY_END STAT WORD Modbus Function code 02h end register for Mx.y
Default: 39999
FC4_ADDR_INPUT_START STAT WORD Modbus Function code 04h start register for IW0
Default: 0
FC4_ADDR_INPUT_END STAT WORD Modbus Function code 04h end register for IWx
Default: 19999
FC4_ADDR_MEMORY_START STAT WORD Modbus Function code 04h start register for MW0
Default: 20000
FC4_ADDR_MEMORY_END STAT WORD Modbus Function code 04h end register for MWx
Default: 39999
FC5_ADDR_OUTPUT_START STAT WORD Modbus Function code 05h start register for Q0.0
Default: 0
FC5_ADDR_OUTPUT_END STAT WORD Modbus Function code 05h end register for Qx.y
Default: 19999
FC5_ADDR_MEMORY_START STAT WORD Modbus Function code 05h start register for M0.0
Default: 20000
FC5_ADDR_MEMORY_END STAT WORD Modbus Function code 05h end register for Mx.y
Default: 39999
FC15_ADDR_OUTPUT_START STAT WORD Modbus Function code 0Fh start register for Q0.0
Default: 0
FC15_ADDR_OUTPUT_END STAT WORD Modbus Function code 0Fh end register for Qx.y
Default: 19999
VIPA SPEED7
Modbus Communication
TCP > FB 71 - TCP_MB_SERVER - Modbus/TCP server
HB00 | OPL_SP7 | Operation list | en | 18-30 187