UDT - Header Declaration Data type Description
ProtocollMajor OUTPUT Byte Protocol version: Major
ProtocollMinor OUTPUT Byte Protocol version: Minor
ProtocollRevsion OUTPUT Byte Protocol version: Revision
ChipDateYear OUTPUT WORD Date measuring chip: Year
ChipDateMonth OUTPUT Byte Date measuring chip: Month
ChipDateDay OUTPUT Byte Date measuring chip: Day
Same data structure for the individual measurands. An overview of the measurands can be found in the manual for your
energy measurement module.
UDT - Data Declaration Data type Description
Name IN_OUT STRUCT
n Name of the measurand
Read_Mode INPUT BYTE
n Bit 0: Accessing the measured value of the measurand
– 0: Measured value should not be read.
– 1: Measured value should be read.
Value OUTPUT DWORD
n Current measured value
UDT - SetValues Declaration Data type Description
SetValues
STRUCT
EN_L1_CON-
SUMED
INPUT DWORD Setpoint active energy L1 consumer: UINT32, 1Wh
EN_L1_ DELIV-
ERED
INPUT DWORD Setpoint active energy L1 producer: UINT32, 1Wh
EN_L2_CON-
SUMED
INPUT DWORD Setpoint active energy L2 consumer: UINT32, 1Wh
EN_L2_ DELIV-
ERED
INPUT DWORD Setpoint active energy L2 producer: UINT32, 1Wh
EN_L3_CON-
SUMED
INPUT DWORD Setpoint active energy L3 consumer: UINT32, 1Wh
EN_L3_ DELIV-
ERED
INPUT DWORD Setpoint active energy L3 producer: UINT32, 1Wh
EXCESS_ACTIVE_
EN_CONSUME
INPUT DWORD Setpoint for overflow energy meter phase 1 ... 3 consumer
n 0xXX112233
– XX: not used
– 11: Setpoint (byte) for overflow energy meter phase 1 consumer
– 22: Setpoint (byte) for overflow energy meter phase 2 consumer
– 33: Setpoint (byte) for overflow energy meter phase 3 consumer
Is incremented by 1 in case of an overflow of the energy meter (ID = 1)
EXCESS_ACTIVE_
EN_DELIVERED
INPUT DWORD Setpoint for overflow energy meter phase 1 ... 3 producer
n 0xXX112233
– XX: not used
– 11: Setpoint (byte) for overflow energy meter phase 1 producer
– 22: Setpoint (byte) for overflow energy meter phase 2 producer
– 33: Setpoint (byte) for overflow energy meter phase 3 producer
Is incremented by 1 in case of an overflow of the energy meter (ID = 2)
VIPA SPEED7
Device Specific
Energy Measurement > UDT 325 - EM_DATA_R1 - Data structure for FB 325
HB00 | OPL_SP7 | Operation list | en | 18-30 270