No. Designation Range of
values
Setting for Simple Motion Control Library
H5-04 Stop method after communication error
(CE error)
0, 1, 2, 3
n 3: Operation continues with alarm
H5-05 Stop method after communication error
(CE error)
0, 1
n 1: Activated - If the connection is aborted for
longer than 2s (adjustable via H2-09), a CE
error is triggered.
H5-06 Waiting time between receiving and
sending data from the inverter drive
5 ... 65ms
n 5ms
H5-07 Request to send (RTS) control 0, 1
n 1: Activated - RTS is activated only when
sending (RS485 or RS422 and multi-drop)
H5-09 Time after which a communication error
(CE error) is detected.
0,0 ... 10,0s
n 2s
H5-10 Step size (resolution) for the MEM-
OBUS/Modbus register 0025h
0, 1 By default, the resolution is set to 0.1V increments
(0).
n 0: 0.1V increments
n 1: 1V increments
H5-11 ENTER function for connections 0, 1
n 1: Enter command not required
H5-12 Selection start command method 0, 1
n 1: Run/Stop
B1-01 Input source frequency setpoint 1 0, 1, 2, 3, 4
n 2: MEMOBUS/Modbus communication
B1-02 Input source start command 1 0, 1, 2, 3
n 2: MEMOBUS/Modbus communication
B1-15 Input source frequency setpoint 2 0, 1, 2, 3, 4
n 2: MEMOBUS/Modbus communication
B1-16 Input source start command 2 0, 1, 2, 3
n 2: MEMOBUS/Modbus communication
For all settings to be accepted, you must restart the inverter drive after
parametrization!
VIPA SPEED7
Motion control - Simple Motion Control Library
Usage inverter drive via Modbus RTU > Set the parameters on the inverter drive
HB00 | OPL_SP7 | Operation list | en | 18-30 453