13.5.5.2.2 Hardware configuration System SLIO CPU 013C
To be compatible with the Siemens SIMATIC Manager the following steps should be exe-
cuted:
1. Start the Siemens hardware configurator with a new project.
2. Insert a profile rail from the hardware catalog.
3. Place at ‘Slot’ -Number 2 the CPU 314C-2 PN/DP (314-6EH04-0AB0 V3.3).
4. Click at the sub module ‘PN-IO’ of the CPU.
5.
Select ‘Context menu è Insert PROFINET IO System’.
6. Use [New] to create a new subnet and assign valid IP address data for your
PROFINET system.
7. Click at the sub module ‘PN-IO’ of the CPU and open with ‘Context menu
è Properties’ the properties dialog.
8. Enter at ‘General’ a ‘Device name’ . The device name must be unique at the
Ethernet subnet.