Specific error information:
Value Description
0000h Processing completed without errors.
7000h Call issued with REQ = 0 (call without processing),
BUSY is set to 0, no data transfer is active.
7001h First call with REQ = 1: data transfer initiated;
BUSY is set to 1.
7002h Intermediate call (REQ irrelevant): data transfer active;
BUSY is set to 1.
8090h The specified target address of the communication partners is not valid, e.g.
n bad IOID
n bad base address exists
n bad MPI-address (> 126)
8092h Error in SD or RD, e.g.:
n illegal length of SD
n SD = NIL is not permitted
8095h The block is already being processed on a priority class that has a lower priority.
80A0h The data type specified by SD of the sending CPU is not supported by the communication partner.
80A1h Communication failures: SFC-call after an existing connection has been terminated.
80B0h Object cannot be found, e.g. DB was not loaded.
80B1h ANY-pointer error. The length of the data block that must be transferred is wrong.
80B2h HW-error: module does not exist
n the slot that was configured is empty.
n Actual module type does not match the required module type.
n Decentralized periphery not available.
n The respective SDB does not contain an entry for the module.
80B3h Data can either be read or written, e.g. write protected DB.
80B4h The communication partner does not support the data type specified in VAR_ADDR.
80B6h The received acknowledgement contains an unknown error code.
80B7h Data type and / or the length of the transferred data does not fit the buffer in the partner CPU where the
data must be written.
80BAh The answer of the communication partner does not fit into the communication telegram.
80C0h The specified connection is already occupied by another operation.
80C1h Lack of resources on the CPU where the SFC is being executed, e.g.:
n the module is already executing the maximum number of different send operations.
n connection resources may be occupied, e.g. by a receive operation.
VIPA SPEED7
Integrated Standard
System Functions > SFC 68 - X_PUT - Write data
HB00 | OPL_SP7 | Operation list | en | 18-30 713