AINFO PROFINET IO: Data structure of the target area (interrupt information)
Byte Declaration Data type Description
6 ... 7 Interrupt type WORD Identifier for the interrupt type:
1: Diagnostic interrupt (incoming)
2: Hardware interrupt
3: Removal interrupt
4: Insertion interrupt
5: Status interrupt
6: Update interrupt
7: Redundancy interrupt
8: Controlled by supervisor
9: Released by supervisor
10: Configured module not inserted
11: Return of submodule
12: Diagnostic interrupt (exiting state)
13: Direct data exchange connection message
14: Neighbourhood change message
15: Clock synchronization message (from bus)
16: Clock synchronization message (from device)
17: Network component message
18: Time synchronization message (from bus)
19 to 31: Reserved
32 to 127: Vendor-specific interrupt
128 ... 65535: reserved, without the following VIPA specific inter-
rupt types:
38CAh: Recovery of the controller
48CAh: Configuration of the controller accepted
39CAh: Controller failure
49CAh: Failure of the controller due to the watchdog
38CBh: Recovery of the device
38CCh: Failure of the recovery of the device
38CDh: Another device is detected during the recovery of the
device.
38CEh: Parameter error during the recovery of the device
39CBh: Device failure
8 ... 11 API DWORD API (Application Process Identifier)
12 ... 13 Slot number WORD Slot number of the component triggering the interrupt (range of
values 0 to 65535)
14 ... 15 Interface module
slot number
WORD Interface module slot number of the component triggering the inter-
rupt (range of values 0 to 65535)
16 ... 19 Module ID DWORD Specific information on the source of the interrupt: Module ID
VIPA SPEED7
Integrated Standard
System Function Blocks > SFB 54 - RALRM - Receiving an interrupt from a periphery module
HB00 | OPL_SP7 | Operation list | en | 18-30 785