EasyManua.ls Logo

YASKAWA VIPA SPEED7 - Page 892

YASKAWA VIPA SPEED7
1007 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
This is a normal system message. This order is a READ/WRITEPASSIV and can not
be started from the AG.
F - Order not foundThe called order is not parameterized on the CP. This error may
occur when the SSNR/A-No. combination in the handling block is wrong or no con-
nection block is entered.
The bits 4 to 7 of byte 2 are reserved for extensions.
Here you may see if an order has already been started, if an error occurred or if this order
is blocked, e.g. a virtual connection doesn’t exist any longer.
n Bit 0 - Handshake convenient
Set:
Per plug-in according to the "delete"-announcement in the order status bit: Hand-
shake convenient (= 1) is used at the RECEIVE block (telegram exists at PRIO 1
or RECEIVE impulse is possible at PRIO 2/3)
Analyze:
Per RECEIVE block: The RECEIVE initializes the handshake with the CP only if
this bit is set. Per application: for RECEIVE request (request a telegram at PRIO
1).
n Bit 1 - Order is running
Set:
Per plug-in: when the CP received the order.
Delete:
Per plug-in: when an order has been commissioned (e.g. receipt received).
Analyze:
Per handling blocks: A new order is only send, when the order before is com-
pletely commissioned. Per user: when you want to know, if triggering a new order
is convenient.
n Bit 2 - Order ready without errors
Set:
Per plug-in: when the according order has been commissioned without errors.
Delete:
Per plug-in: when the according order is triggered for a second time.
Analyze:
Per user: to proof that the order has been commissioned without errors.
n Bit 3 - Order ready with errors
Set:
Per plug-in: when the according order has been commissioned with errors. Error
causes are to find encrypted in the high-part of the indicator word.
Delete:
Per plug-in: when the according order is triggered for a second time.
Analyze:
Per user: to proof that the order has been commissioned with errors. If set, the
error causes are to find in the highbyte of the indicator word.
Status management Byte
1, Bit 0 ... Bit 3
VIPA SPEED7
System Blocks
Fetch/Write Communication > SFC 230 ... 238 - Page frame communication
HB00 | OPL_SP7 | Operation list | en | 18-30 892