This is a normal system message. This order is a READ/WRITEPASSIV and can not
be started from the AG.
F - Order not foundThe called order is not parameterized on the CP. This error may
occur when the SSNR/A-No. combination in the handling block is wrong or no con-
nection block is entered.
The bits 4 to 7 of byte 2 are reserved for extensions.
Here you may see if an order has already been started, if an error occurred or if this order
is blocked, e.g. a virtual connection doesn’t exist any longer.
n Bit 0 - Handshake convenient
– Set:
Per plug-in according to the "delete"-announcement in the order status bit: Hand-
shake convenient (= 1) is used at the RECEIVE block (telegram exists at PRIO 1
or RECEIVE impulse is possible at PRIO 2/3)
– Analyze:
Per RECEIVE block: The RECEIVE initializes the handshake with the CP only if
this bit is set. Per application: for RECEIVE request (request a telegram at PRIO
1).
n Bit 1 - Order is running
– Set:
Per plug-in: when the CP received the order.
– Delete:
Per plug-in: when an order has been commissioned (e.g. receipt received).
– Analyze:
Per handling blocks: A new order is only send, when the order before is com-
pletely commissioned. Per user: when you want to know, if triggering a new order
is convenient.
n Bit 2 - Order ready without errors
– Set:
Per plug-in: when the according order has been commissioned without errors.
– Delete:
Per plug-in: when the according order is triggered for a second time.
– Analyze:
Per user: to proof that the order has been commissioned without errors.
n Bit 3 - Order ready with errors
– Set:
Per plug-in: when the according order has been commissioned with errors. Error
causes are to find encrypted in the high-part of the indicator word.
– Delete:
Per plug-in: when the according order is triggered for a second time.
– Analyze:
Per user: to proof that the order has been commissioned with errors. If set, the
error causes are to find in the highbyte of the indicator word.
Status management Byte
1, Bit 0 ... Bit 3
VIPA SPEED7
System Blocks
Fetch/Write Communication > SFC 230 ... 238 - Page frame communication
HB00 | OPL_SP7 | Operation list | en | 18-30 892